- 6 -
eFlow6N Series Installation Guide
NC C NO
NC C NO
BAT FAIL
AC FAIL
POWER
SOURCE
RED INDICATING
LAMP
Fig. 1 -
eFlow6N Board configuration
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Trouble/Time Limited Warning of Stand-by Batteries:
For compliance with ULC S318-96, the Time Limited Warning circuit must be connected for local or remote annun-
ciation with an Amber or Red LED to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by
battery has been depleted). Connect the circuit to the Batt Fail relay contacts to an appropriate input of a UL Listed
Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed for local annunciation.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Fig. 2 -
Battery trouble indication -
For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure.
Wire one leg of a UL Listed, power-limited power source to the indicating lamp.
Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact
terminals marked [BAT FAIL - C, NO] (Fig. 2, pg. 6).