- 4 - 

eFlow6N Series Installation Guide

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to 

 

qualified service personnel.

 

For Fire Alarm applications the outputs are “Special Applications” only, see list 

(refer to Appendix A, pg. 12)

4.  Measure output voltage before connecting devices. This helps avoiding potential damage.

5.  Connect devices to be powered:

 

a.  For eFlow6N/eFlow6NX connect devices to terminals marked [– DC +] (

Fig. 1h, pg. 6

). 

 

b.  For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked  

 

  [1P & 1N] through [8P & 8N] 

(Fig. 3a & 3b, pg. 6) 

or 1 to 16 marked [1P & 1N] through [16P & 16N]

 

  (Fig. 4a & 4b, pg. 6)

 carefully observing correct polarity.

 

For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm 

 

Interface. Connect device to terminals marked [+ AUX –] 

(Fig. 1f, pg. 6).

6.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 

 

in the loss of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel 

 

type. Connect battery to terminals marked [– BAT +] 

(Fig. 1g, pg. 6)

. Use two (2) 12VDC batteries 

 

connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), 

 

CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 

 

batteries of an appropriate rating.

7.  Connect appropriate signaling notification devices to AC FAIL & BAT FAIL 

(Fig. 1b, pg. 6)

 supervisory

 

relay outputs.

8.  To delay AC reporting for 2 hrs. set DIP switch [AC Delay] to OFF position 

(Fig. 1c, pg. 6)

.

 

To delay AC reporting for 1 min. set DIP switch [AC Delay] to ON position 

(Fig. 1c, pg. 6)

.

 

Note: 

Must be set to ON position for Burglar Alarm Applications.

9.  To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position 

(Fig. 1c, pg. 6)

.

 

To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position 

(Fig. 1c, pg. 6)

.

10.  Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals 

 

will cause [DC] output to shutdown 

(Fig. 1d, pg. 6)

.

11.  Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching

 

[Trigger EOL Shutdown] 

(Fig. 1e, pg. 6)

.

12.  For Access Control Applications: mount UL Listed tamper switch (Altronix model TS112 or equivalent) at 

 

the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right 

 side 

(Fig. 5, pg. 8 or Fig. 7, pg. 10)

. Connect tamper switch wiring to the Access Control Panel input or the 

 

appropriate UL Listed reporting device.

Wiring:

Use 18 AWG or larger for all low voltage power connections.

Note:

 Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

 Under normal load conditions, the DC output voltage should be checked for proper 

 

 

 

voltage level eFlow6N: 12VDC or 24VDC nominal rated @ 6A max.

Battery Test:

 

Under normal load conditions check that the battery is fully charged, check specified 

 

 

 

voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at battery terminal and at the board 

 

 

 

terminals marked [– BAT +] to ensure that there is no break in the battery connection wires.

Note:

 Maximum charging current under discharges is 1.54A.

Note:

 Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.

Содержание eFlow6N

Страница 1: ...VDC Eight 8 PTC Protected Class 2 Power Limited Outputs eFlow6N16D eFlow6NX16D 6A 12VDC or 24VDC Sixteen 16 PTC Protected Class 2 Power Limited Outputs eFlow6N Series Power Supply Chargers Models Incl...

Страница 2: ...The following units provide non power limited outputs eFlow6N eFlow6NX eFlow6N8 eFlow6NX8 eFlow6N16 and eFlow6NX16 The following units provide Class 2 power limited outputs eFlow6N8D eFlow6NX8D eFlow6...

Страница 3: ...can be seen through the LED lens on the door of the enclosure Use 14 AWG or larger for all power connections Secure green wire lead to earth ground Keep power limited wiring separate from non power l...

Страница 4: ...Delay to OFF position Fig 1c pg 6 To delay AC reporting for 1 min set DIP switch AC Delay to ON position Fig 1c pg 6 Note Must be set to ON position for Burglar Alarm Applications 9 To enable Fire Ala...

Страница 5: ...mally closed from an FACP output circuit power limited input Fig 1d pg 6 NO GND RESET FACP interface latching or non latching power limited Fig 1e pg 6 AUX Auxiliary Class 2 power limited output rated...

Страница 6: ...e input of a UL Listed Burglar Alarm or Access Control Panel The following figure shows the circuitry needed for local annunciation Fig 2 Battery trouble indication For Canadian use a red indicating l...

Страница 7: ...ses with the same type and rating 3 5A 250V N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs From Power Supply...

Страница 8: ...argeable Stand by Battery for UL294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand...

Страница 9: ...ade employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian...

Страница 10: ...4 Applications Note 12V batteries required for ULC S319 installations CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power limited wiring separate from non...

Страница 11: ...de employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian i...

Страница 12: ...electric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24...

Страница 13: ...6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35...

Страница 14: ...34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12...

Страница 15: ...mote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Страница 16: ...6A 6A 1 5A 6A Over 4 Hours 6A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Transfer...

Отзывы: