- 4 -
eFlow6N Series Installation Guide
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or
servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to
qualified service personnel.
For Fire Alarm applications the outputs are “Special Applications” only, see list
(refer to Appendix A, pg. 12)
.
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Connect devices to be powered:
a. For eFlow6N/eFlow6NX connect devices to terminals marked [– DC +] (
Fig. 1h, pg. 6
).
b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked
[1P & 1N] through [8P & 8N]
(Fig. 3a & 3b, pg. 6)
or 1 to 16 marked [1P & 1N] through [16P & 16N]
(Fig. 4a & 4b, pg. 6)
carefully observing correct polarity.
For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm
Interface. Connect device to terminals marked [+ AUX –]
(Fig. 1f, pg. 6).
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result
in the loss of the output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel
type. Connect battery to terminals marked [– BAT +]
(Fig. 1g, pg. 6)
. Use two (2) 12VDC batteries
connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH),
CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2
batteries of an appropriate rating.
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL
(Fig. 1b, pg. 6)
supervisory
relay outputs.
8. To delay AC reporting for 2 hrs. set DIP switch [AC Delay] to OFF position
(Fig. 1c, pg. 6)
.
To delay AC reporting for 1 min. set DIP switch [AC Delay] to ON position
(Fig. 1c, pg. 6)
.
Note:
Must be set to ON position for Burglar Alarm Applications.
9. To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position
(Fig. 1c, pg. 6)
.
To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position
(Fig. 1c, pg. 6)
.
10. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals
will cause [DC] output to shutdown
(Fig. 1d, pg. 6)
.
11. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching
[Trigger EOL Shutdown]
(Fig. 1e, pg. 6)
.
12. For Access Control Applications: mount UL Listed tamper switch (Altronix model TS112 or equivalent) at
the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the right
side
(Fig. 5, pg. 8 or Fig. 7, pg. 10)
. Connect tamper switch wiring to the Access Control Panel input or the
appropriate UL Listed reporting device.
Wiring:
Use 18 AWG or larger for all low voltage power connections.
Note:
Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test:
Under normal load conditions, the DC output voltage should be checked for proper
voltage level eFlow6N: 12VDC or 24VDC nominal rated @ 6A max.
Battery Test:
Under normal load conditions check that the battery is fully charged, check specified
voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at battery terminal and at the board
terminals marked [– BAT +] to ensure that there is no break in the battery connection wires.
Note:
Maximum charging current under discharges is 1.54A.
Note:
Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.