eFlow6N Series Installation Guide 

- 5 -

LED Diagnostics:

Power Supply/Charger

Red (DC)

Green (AC/AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module

Green (AC)

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

Terminal Identification:

Power Supply/Charger

Terminal Legend

Function/Description

L, N

Connect 120VAC 60Hz to these terminals: L to hot, N to neutral (non power-limited) 

(Fig. 1a, pg. 6)

.

– DC +

12VDC or 24VDC nominal @ 6A continuous output (power-limited output) 

(Fig. 1h, pg. 6)

.

Trigger EOL

Supervised

Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open, 

normally closed from an FACP output circuit (power-limited input) 

(Fig. 1d, pg. 6)

.

NO, GND RESET

FACP interface latching or non-latching (power-limited) 

(Fig. 1e, pg. 6)

.

+ AUX –

Auxiliary Class 2 power-limited output rated @ 1A (unswitched) 

(Fig. 1f, pg. 6)

.

AC Fail 

NC, C, NO

Indicates loss of AC power, e.g. connect to audible device or alarm panel. 

Relay normally energized when AC power is present. 

Contact rating 1A @ 30VDC (power-limited) 

(Fig. 1b, pg. 6)

.

Bat Fail

NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized 

when DC power is present. Contact rating 1A @ 30VDC. 

A removed battery is reported within 5 minutes.

Battery reconnection is reported within 1 minute (power-limited) 

(Fig. 1b, pg. 6)

.

– BAT +

Stand-by battery connections. Maximum charge current 1.54A (non power-limited)

(Fig. 1g, pg. 6)

.

Power Distribution Module

Terminal Legend

PD8UL/PD8ULCB

Terminal Legend

PD16W/PD16WCB

Function/Description

1P to 8P

1P to 16P

Positive DC power outputs.

1N to 8N

1N to 16N

Negative DC power outputs.

Содержание eFlow6N

Страница 1: ...VDC Eight 8 PTC Protected Class 2 Power Limited Outputs eFlow6N16D eFlow6NX16D 6A 12VDC or 24VDC Sixteen 16 PTC Protected Class 2 Power Limited Outputs eFlow6N Series Power Supply Chargers Models Incl...

Страница 2: ...The following units provide non power limited outputs eFlow6N eFlow6NX eFlow6N8 eFlow6NX8 eFlow6N16 and eFlow6NX16 The following units provide Class 2 power limited outputs eFlow6N8D eFlow6NX8D eFlow6...

Страница 3: ...can be seen through the LED lens on the door of the enclosure Use 14 AWG or larger for all power connections Secure green wire lead to earth ground Keep power limited wiring separate from non power l...

Страница 4: ...Delay to OFF position Fig 1c pg 6 To delay AC reporting for 1 min set DIP switch AC Delay to ON position Fig 1c pg 6 Note Must be set to ON position for Burglar Alarm Applications 9 To enable Fire Ala...

Страница 5: ...mally closed from an FACP output circuit power limited input Fig 1d pg 6 NO GND RESET FACP interface latching or non latching power limited Fig 1e pg 6 AUX Auxiliary Class 2 power limited output rated...

Страница 6: ...e input of a UL Listed Burglar Alarm or Access Control Panel The following figure shows the circuitry needed for local annunciation Fig 2 Battery trouble indication For Canadian use a red indicating l...

Страница 7: ...ses with the same type and rating 3 5A 250V N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs From Power Supply...

Страница 8: ...argeable Stand by Battery for UL294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand...

Страница 9: ...ade employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian...

Страница 10: ...4 Applications Note 12V batteries required for ULC S319 installations CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power limited wiring separate from non...

Страница 11: ...de employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian i...

Страница 12: ...electric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24...

Страница 13: ...6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35...

Страница 14: ...34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12...

Страница 15: ...mote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Страница 16: ...6A 6A 1 5A 6A Over 4 Hours 6A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Transfer...

Отзывы: