eFlow6N Series Installation Guide 

- 11 -

NEC Power-Limited Wiring Requirements for eFlow6NX Models:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit 

wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited 

circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. 

One such example of this is shown below. Your specific application may require different conduit knockouts to 

be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field 

wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).

Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.

For Canadian installations use shielded wiring for all connections.

Note:

 Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire 

(Fig. 8a).

Fig. 8

Fig. 8a

Input

120VAC 60Hz

(non power-

limited)

Supervisory, Fire Alarm Interface

and Aux. output Connections

(power-limited)

DC Output*

Power 

Distribution

Optional UL 

Listed Battery 

Enclosure

(non power-

limited)

*  Outputs are non power-limited:

  eFlow6NX, eFlow6NX8, eFlow6NX16.

  Outputs are Class 2 power-limited:

  eFlow6NX8D, eFlow6NX16D.

Battery

Connections

(non power-limited)

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

Содержание eFlow6N

Страница 1: ...VDC Eight 8 PTC Protected Class 2 Power Limited Outputs eFlow6N16D eFlow6NX16D 6A 12VDC or 24VDC Sixteen 16 PTC Protected Class 2 Power Limited Outputs eFlow6N Series Power Supply Chargers Models Incl...

Страница 2: ...The following units provide non power limited outputs eFlow6N eFlow6NX eFlow6N8 eFlow6NX8 eFlow6N16 and eFlow6NX16 The following units provide Class 2 power limited outputs eFlow6N8D eFlow6NX8D eFlow6...

Страница 3: ...can be seen through the LED lens on the door of the enclosure Use 14 AWG or larger for all power connections Secure green wire lead to earth ground Keep power limited wiring separate from non power l...

Страница 4: ...Delay to OFF position Fig 1c pg 6 To delay AC reporting for 1 min set DIP switch AC Delay to ON position Fig 1c pg 6 Note Must be set to ON position for Burglar Alarm Applications 9 To enable Fire Ala...

Страница 5: ...mally closed from an FACP output circuit power limited input Fig 1d pg 6 NO GND RESET FACP interface latching or non latching power limited Fig 1e pg 6 AUX Auxiliary Class 2 power limited output rated...

Страница 6: ...e input of a UL Listed Burglar Alarm or Access Control Panel The following figure shows the circuitry needed for local annunciation Fig 2 Battery trouble indication For Canadian use a red indicating l...

Страница 7: ...ses with the same type and rating 3 5A 250V N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs From Power Supply...

Страница 8: ...argeable Stand by Battery for UL294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand...

Страница 9: ...ade employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian...

Страница 10: ...4 Applications Note 12V batteries required for ULC S319 installations CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power limited wiring separate from non...

Страница 11: ...de employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian i...

Страница 12: ...electric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24...

Страница 13: ...6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35...

Страница 14: ...34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12...

Страница 15: ...mote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Страница 16: ...6A 6A 1 5A 6A Over 4 Hours 6A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Transfer...

Отзывы: