AL400X220 Series
- 5 -
LED Diagnostics:
Power Supply Board
Red (DC)
Green (AC)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Red (Bat)
Battery Status
ON
Normal operating condition.
OFF
Battery fail/low battery.
Power Distribution Module
Green
Power Distribution Module Status
ON
Normal operating condition.
OFF
No Power Output.
Terminal Identification:
Power Supply Board
Terminal Legend Function/Description
L, G, N
Connect 220VAC (working range 198VAC - 256VAC), 50/60Hz to these terminals:
L to Hot, N to Neutral. Do not use the [G] terminal.
+ DC –
12VDC @ 4A or 24VDC @ 3A continuous power-limited output.
AC Fail
NC, C, NO
Indicates loss of AC power, e.g. connect to annunciator/alarm panel. Relay normally ener-
gized when AC power is present. Contact rating 1A @ 28VDC. AC Fail condition will report
approximately within one (1) minute after loss of AC. To delay report for 6 hours cut jumper
J1 on the Power Supply Board (AC trouble output delay option). If this mode is selected, the
Power Supply Board must be reset by removing all power to it for 30 seconds.
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized
when DC power is present. Contact rating 1A @ 28VDC. Low battery conditions will report
approximately 21VDC (24VDC output setting) or approximately 10.5VDC (12VDC output
setting). Battery presence detection will report approximately 1 minute after battery remains
undetected (missing or removed).
+ BAT –
Stand-by battery connections. Maximum charge current 0.7A.
Power Distribution Module
Terminal Legend
Function/Description
PD4/PD4CB
PD8/PD8CB
1P to 4P
1P to 8P
Positive DC power outputs.
1N to 4N
1N to 8N
Negative DC power outputs.