AL400X220 Series 

- 3 -

Power Supply Output Specifications:

Output

Switch Position

12VDC

SW1 - ON

24VDC

SW1 - OFF

Stand-by Specifications 

(total current shown)

:

Output

4 hr. of Stand-by and

5 Minutes of Alarm

24 hr. of Stand-by and

5 Minutes of Alarm

60 hr. of Stand-by and

5 Minutes of Alarm

12VDC / 40AH Battery

Stand-by = 4.0A

Alarm = 4.0A

Stand-by = 1.0A

Alarm = 4.0A

Stand-by = 300mA

Alarm = 4.0A

24VDC / 12AH Battery

Stand-by = 200mA

Alarm = 3.0A

24VDC / 40AH Battery

Stand-by = 3.0A

Alarm = 3.0A

Stand-by = 1.0A

Alarm = 3.0A

Stand-by = 300mA

Alarm = 3.0A

ON

OFF - 24V

ON - 12V

Fig. 1a

Fig. 1b

Fig. 1c

L       G        

N

BAT FAIL  NC  C  NO  NC  C  NO 

 

AC  FAIL

AC

+ BAT -

+ DC -

DC

BAT

F1

Off - 24V

On - 12V

SW1

ON

Switch Position:

24VDC = SW1 OFF

12VDC = SW1 ON

Battery & AC

Supervision Circuit

J1

AC Delay

Power

Distribution

Module(s)

Ground

Lug

220VAC

power mains

Battery connection

CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.

For 12VDC Operation

use hook-up in the

inset on the right

12VDC Rechargeable Battery

(optional)

12VDC Rechargeable Battery

(optional)

OFF - 24V

ON - 12V

SW1

ON

1

CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric
shock and fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture.

Battery & AC

Supervision Circuit

NC  C  NO NC  C  NO  

J1

AC Delay

Fig. 1 - 

AL400X220 Series

Содержание AL400X220 Series

Страница 1: ...nclude For a red enclosure add an R suffix to the part e g AL400PD8R220 For a larger enclosure add an X suffix to the part e g AL400XPD8220 Installation Guide AL400X220 Single Output AL400PD4220 Four...

Страница 2: ...D8220 Two 2 12VDC 12AH AL400PD8CB220 PD8CB P 2 5A Two 2 12VDC 7AH AL400XPD8CB220 Two 2 12VDC 12AH AL400XPD16220 Two PD8 16 P 3 5A 12VDC 3A 24VDC Two 2 12VDC 12AH AL400XPD16CB220 Two PD8CB P 2 5A Two 2...

Страница 3: ...DC DC BAT F1 Off 24V On 12V SW1 ON Switch Position 24VDC SW1 OFF 12VDC SW1 ON Battery AC Supervision Circuit J1 AC Delay Power Distribution Module s Ground Lug 220VAC power mains Battery connection CA...

Страница 4: ...hrough 8P 8N Fig 3a 3b pg 6 carefully observing correct polarity 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output vol...

Страница 5: ...larm panel Relay normally ener gized when AC power is present Contact rating 1A 28VDC AC Fail condition will report approximately within one 1 minute after loss of AC To delay report for 6 hours cut j...

Страница 6: ...stalled Replace fuses with the same type and rating 3 5A 250V N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs...

Страница 7: ...82 6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40...

Страница 8: ...4 5mm 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1...

Отзывы: