Installation Instructions:

Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all 

local codes and authorities having jurisdiction. Product is intended for indoor use only. 

1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes

  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 

  two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place enclosure’s upper 

  keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pg. 7-8).

2. Connect AC circuit (220VAC, 50/60Hz) as follows: Green branch wire connects to earth (safety) ground 

  lug    . Line and Neutral to the connector on power supply board marked [L, N] respectively 

(Fig. 1, pg. 3)

  Use 14 AWG or larger for all power connections (Battery, DC output, AC input).

  Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

 

Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input, 

  Battery Wires). Minimum 0.25” spacing must be provided.

  CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 

  equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified 

  service personnel.

3. Set the unit to the desired DC output voltage by setting SW1

 (Fig. 1c, pg. 3)

 to the appropriate position

 

(

Power Supply Voltage Output Specifications Chart

, pg. 2).

4. Measure output voltage before connecting any devices to ensure proper operation. Improper or high voltage 

  will damage these devices. When servicing the unit, AC mains should be removed.

5. Connect devices to be powered:

  a. For AL400X220 Power Supply: connect devices to the terminals marked [+ DC –] (

Fig. 1, pg. 3

). 

  b. For other Power Distribution Models: connect devices to be powered to the terminal pairs 1 to 4 marked  

    [1P & 1N] through [4P & 4N] (

Fig. 2a & 2b, pg. 6

) or 1 to 8 marked [1P & 1N] through [8P & 8N]

    (Fig. 3a & 3b, pg. 6),

 carefully observing correct polarity.

6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 

  in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.

7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL

 (Fig. 1a, pg. 3) 

supervisory 

  relay outputs.

 

Note:

 When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be

  utilized to visually indicate that AC power is on. To delay report for 6 hours cut “AC Delay” jumper 

 

(Fig. 1b, pg. 3)

8. Please ensure that the cover is secured with the provided key lock.

Wiring:

Use 14 AWG or larger for all power connections.

Note:

 Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

  Under normal load conditions the DC output voltage should be checked for the proper 

 

voltage level 

(Power Supply Voltage Output Specifications Chart, pg. 3).

Battery Test: 

 Under normal load conditions check that the battery is fully charged, check specified 

 

voltage both at the battery terminal and at the board terminals marked [+ BAT –] to 

 

ensure that there is no break in the battery connection wires.

Note:

  

Maximum charging current under discharges is 0.7A.

Note:

  

Expected battery life is 5 years; however, it is recommended changing batteries in 

 

4 years or less if needed.

L       G        

N

BAT FAIL  NC  C  NO  NC  C  NO 

 

AC  FAIL

AC

+ BAT -

+ DC -

DC

BAT

F1

Off - 24V

On - 12V

SW1

ON

Switch Position:

24VDC = SW1 OFF

12VDC = SW1 ON

Battery & AC

Supervision Circuit

J1

AC Delay

Power

Distribution

Module(s)

Ground

Lug

220VAC

power mains

Battery connection

CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.

For 12VDC Operation

use hook-up in the

inset on the right

12VDC Rechargeable Battery

(optional)

12VDC Rechargeable Battery

(optional)

OFF - 24V

ON - 12V

SW1

ON

1

CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric
shock and fire hazard replace fuse with the same type and rating. Do not expose to rain or moisture.

Battery & AC

Supervision Circuit

NC  C  NO NC  C  NO  

J1

AC Delay

Содержание AL400X220 Series

Страница 1: ...nclude For a red enclosure add an R suffix to the part e g AL400PD8R220 For a larger enclosure add an X suffix to the part e g AL400XPD8220 Installation Guide AL400X220 Single Output AL400PD4220 Four...

Страница 2: ...D8220 Two 2 12VDC 12AH AL400PD8CB220 PD8CB P 2 5A Two 2 12VDC 7AH AL400XPD8CB220 Two 2 12VDC 12AH AL400XPD16220 Two PD8 16 P 3 5A 12VDC 3A 24VDC Two 2 12VDC 12AH AL400XPD16CB220 Two PD8CB P 2 5A Two 2...

Страница 3: ...DC DC BAT F1 Off 24V On 12V SW1 ON Switch Position 24VDC SW1 OFF 12VDC SW1 ON Battery AC Supervision Circuit J1 AC Delay Power Distribution Module s Ground Lug 220VAC power mains Battery connection CA...

Страница 4: ...hrough 8P 8N Fig 3a 3b pg 6 carefully observing correct polarity 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output vol...

Страница 5: ...larm panel Relay normally ener gized when AC power is present Contact rating 1A 28VDC AC Fail condition will report approximately within one 1 minute after loss of AC To delay report for 6 hours cut j...

Страница 6: ...stalled Replace fuses with the same type and rating 3 5A 250V N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs...

Страница 7: ...82 6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40...

Страница 8: ...4 5mm 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1...

Отзывы: