Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

  Under normal load conditions the DC output voltage should be checked for proper 

 

voltage level 

(Stand-by Specifications Chart).

Battery Test:

 

Under normal load conditions check that the battery is fully charged, check specified 

 

voltage both at the battery terminal and at the board terminals marked [– BAT +] to 

 

ensure that there is no break in the battery connection wires.

Note:

 

Maximum charging current under discharge is 500mA.

Note:

 

Expected battery life is 5 years; however, it is recommended changing batteries in 

 

4 years or less if needed.

Terminal Identification:

Terminal Legend

Function/Description

AC/AC

Low voltage AC input (16.5VAC/20VA). UL Listed. Class 2 plug-in transformer.

– DC +

12VDC @ 750mA continuous power-limited output.

– BAT +

Stand-by battery connections. Maximum charge rate 500mA.

AC FAIL

NC, C, NO

Indicates loss of AC, e.g. connect audible device or alarm panel. Relay is normally 

energized when AC power is present. Contact rating 1A @ 28VDC.

LOW BAT

NC, C, NO

Indicates low battery condition e.g connect audible device or alarm panel. 

Relay is normally energized. Contact rating 1A @ 28VDC.

AC 

DC 

AC F

AIL

 

LOW BA

RL2 

RL1 

PTC1 

IC1 

C1 

NO     C     NC 

NO     C     NC 

Class 2

Output

16.5VAC, 20VA

Plug-in Transformer 

(UL Listed Class 2 

Transformer)

750mA 12VDC

Power-Limited Output

Stand-by 

Battery

Fig. 1

Содержание AL100UL

Страница 1: ...ply Charger Installation Guide Rev 050101 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Страница 2: ...or use only 1 Mount the unit in the desired location Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the two upper screws level and secure Mark the position of the lower two holes Remove the enclosure Drill the lower holes and instal...

Страница 3: ...r it is recommended changing batteries in 4 years or less if needed Terminal Identification Terminal Legend Function Description AC AC Low voltage AC input 16 5VAC 20VA UL Listed Class 2 plug in transformer DC 12VDC 750mA continuous power limited output BAT Stand by battery connections Maximum charge rate 500mA AC FAIL NC C NO Indicates loss of AC e g connect audible device or alarm panel Relay is...

Страница 4: ... 153 7mm 3 5 88 9mm Enclosure Dimensions H x W x D 8 5 x 7 5 x 3 5 215 9mm x 190 5mm x 88 9mm The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product s enclosure that may be of sufficient magnitude to constitute an electric shock The exclamation point within an equilateral triangle i...

Отзывы: