- 2 - 

AL100UL Installation Guide

Agency Listings:

•  UL Listed Standard for Power Supplies for Use with 

  Burglar Alarm System Units (UL 603). 

  Burglar Alarm System Power Supply.

•  CUL Listed - CSA Standard

  C603-M1988, Burglar Alarm System.

Input:

•  16.5VAC, 20VA from UL Listed Class 2 

  transformer (sold separately).

Output:

•  12VDC Class 2 Rated power-limited output.

•  750mA continuous supply current at 12.5 to 13.9VDC.

•  Filtered and electronically regulated output.

Supervision:

•  Low battery and AC fail supervision 

  form “C” contacts (1A @ 28VDC).

Battery Backup:

•  Built-in charger for sealed lead acid or 

  gel type batteries.

•  Maximum charge current is 0.5A.

•  Automatic switch over to stand-by battery when 

  AC fails.

•  Low battery disconnect prevents batteries from

  deep discharge.

Visual Indicators:

•  AC input and DC output LED indicators.

Additional Features:

•  Short circuit and thermal overload protection.

•  Unit is complete with power supply and enclosure.

•  Includes battery leads.

Enclosure Dimensions 

(H x W x D approx.)

  8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm).

Overview:

Altronix AL100UL power supply converts 16.5VAC, 20VA to a 12VDC power-limited output (see specifications).

The AL100UL is UL Listed for Burglar Alarm applications.

Specifications:

Stand-by Specifications:

Stand-by Battery

Current Draw

Stand-by Time

Alarm Time

12VDC / 4AH Battery

750mA

4 Hours

15 mins.

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all 

local codes and authorities having jurisdiction. Product is intended for indoor use only. 

1. Mount the unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 

  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the 

  enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two 

  holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper 

  keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pg. 4)

. Secure enclosure to earth ground 

(Fig 1, pg. 2).

2. Connect a 16.5VAC, 20VA Class 2, UL Listed plug-in transformer to the terminals marked [AC, AC] 

(Fig 1, pg. 2)

.

3. Measure output voltage before connecting devices. This helps avoiding potential damage.

4. Connect devices to be powered to the terminals marked [– DC +] 

(Fig 1, pg. 2)

.

5. Connect the stand-by battery to the terminals marked [– BAT +] 

(Fig 1, pg. 2) 

(battery leads included).

6. Connect appropriate signaling notification devices to the AC Fail and Low Bat supervisory relay outputs

  terminals marked [LOW BAT - NC, C, NO, AC FAIL - NC, C, NO] 

(Fig 1, pg. 2)

 

Note:

 To meet UL requirements, AC Supervisory outputs must be connected to the zone of Alarm Control 

  Panel or to visual AC trouble indicator. 

 

Note:

 For Access Control applications batteries are optional. 

  When batteries are not used, a loss of AC will result in the loss of output voltage. 

  When the use of stand-by batteries is desired, they must be lead acid or gel type.

LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Содержание AL100UL

Страница 1: ...ply Charger Installation Guide Rev 050101 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Страница 2: ...or use only 1 Mount the unit in the desired location Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure Install two upper fasteners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the two upper screws level and secure Mark the position of the lower two holes Remove the enclosure Drill the lower holes and instal...

Страница 3: ...r it is recommended changing batteries in 4 years or less if needed Terminal Identification Terminal Legend Function Description AC AC Low voltage AC input 16 5VAC 20VA UL Listed Class 2 plug in transformer DC 12VDC 750mA continuous power limited output BAT Stand by battery connections Maximum charge rate 500mA AC FAIL NC C NO Indicates loss of AC e g connect audible device or alarm panel Relay is...

Страница 4: ... 153 7mm 3 5 88 9mm Enclosure Dimensions H x W x D 8 5 x 7 5 x 3 5 215 9mm x 190 5mm x 88 9mm The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product s enclosure that may be of sufficient magnitude to constitute an electric shock The exclamation point within an equilateral triangle i...

Отзывы: