7.0  HAZARDOUS AREA OPERATION

7.1 The DE-2200 system is CSA certified for CLASS I, DIVISION 2, GROUPS C and D areas

when mounted in a suitable enclosure.

In addition, the following requirements must be met (see NFPA standard no. 493):
1. The low voltage sensor switch wires within the panel enclosure must be kept at least two

(2) inches away from other wiring.  Run the sensor switch wires leaving the panel in a
separate conduit from all other wiring and keep them separate throughout the installation.

2. Wiring to the sensors must have a grade of insulation capable of withstanding an AC

voltage of 500 volts RMS.

3. Sensor wires must be run in separate conduits and junction boxes from high voltage wires

such as ignition, fuel valve, and other high voltage wiring.

WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY AND/OR

SUITABILITY FOR CLASS I, DIV. 2, GROUPS C and D.  
DO NOT DISCONNECT EQUIPMENT IN DIV. 2 ENVIRONMENT UNLESS POWER
IS SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS.

8.0  KEYPAD DESCRIPTION

8.1

The DE-2200 monitor Display Module contains a sixteen-key sealed membrane keypad
which is used to stop, reset and test the system.  The user can also view process information
screens, view channel specifics, cancel timers, and view and edit pertinent operating
parameters.

8.2

STOP - The STOP key is used for a manual stop condition.  By pressing the STOP key, the
monitor activates the configured output modules in the power supply.

8.3

RESET - The RESET key clears all past faulted points and resets all input and output timers
to their preset values.

8.4

TEST - The TEST key disables the output modules and allows the user to fault or test the
input sensors.  Every time the test button is pressed, the test timer resets to its preset value.

8.5

CANCEL TIMERS - The CANCEL TIMERS key cancels all timers.

8.6

VIEW CHAN - The VIEW CHANNELS key allows the user to view the status of any input
channel and its user defined label.

8.7

NEXT -  From the VIEW screen, allows the user to view the next process information screen.
From the MENU screens, the next value to be edited.

8.8

VIEW - The VIEW key allows the user to view the process information screens.

8.9

ENTER - The ENTER key is used to accept a selection and to save a new value in memory.

8.10 ESC - The ESCAPE key enables the user to exit any view channels or menu screens at any

time and return to the previous screen without changing programmed values. 

Содержание DE-2200

Страница 1: ...splay Module DE 2200 a Power Supply Module 691122 1 and a Terminal Module 691136 1 These components are interconnected by means of Cable assembly 693115 1 WARNING THE MONITOR SYSTEM MUST BE CONFIGURED PRIOR TO USE ON A COMPRESSOR SYSTEM REFERENCE DE 2200 PI PROGRAMMING INSTRUCTIONS FOR INSTRUCTIONS DESCRIBING HOW TO CONFIGURE THE MONITOR FOR THE SPECIFIC APPLICATION VERIFY THE PROGRAM IN NONVOLATI...

Страница 2: ...dition when the unit is unpowered The output modules can be software configured for either normally open N O or normally closed N C operation and have an LED indicator associated with them Outputs 3 and 4 are for use with the optional speed switch and pre post lube features respectively If an Output Module is programmed for normally closed energized for run the LED will be ON in the normal run con...

Страница 3: ...7 and 40 45 accept 0 5 VDC transducers or industry standard type J or K thermocouples Connections from the Terminal Module to the Display Module are made using the 693115 x series Cable Assembly 4 4 2 The DE 2200 is designed to operate with industry standard voltage or current amplified output transducers in the range of 0 to 5 Vdc or 0 to 25 mA Four series of transducers are available from Altron...

Страница 4: ...e in the panel either on the bottom or the side of the main panel The Terminal Module and Power Supply Module are made to be rail mounted onto commercially available 32 or 35 mm DIN mounting rails The Terminal Module is made to plug directly into the Power Supply Module using the DB 25 D Sub connectors and held together with screws and screw locks Two end brackets P N 610751 should be used to secu...

Страница 5: ... respectively with PRE POST LUBE disabled With PRE POST LUBE enabled Reset is wired to a lube switch Sensor inputs 10 27 can be user configurable as class A class B or class C logic Any sensor point can be wired for normally open or normally closed operation Any unused sensor input must contain a short jumper wire across the input Normally Open N O sensor switches are wired with one wire to the bo...

Страница 6: ...vailable to power the Altronic transducers see wiring diagrams If the 5 volt sensor supply exits the panel it must be fused with a 0 5 ampere fuse If 24 volt powered sensors are used the 24 volt supply to them must be fused appropriately Take care not to damage the insulation when installing and take precautions against later damage from vibration abrasion or liquids in conduits In addition it is ...

Страница 7: ...he four output slots OUT 1 through OUT 4 691065 This module is rated for 24 280 Vac 2 0 A and may be used in any of the four output slots OUT 1 through OUT 4 NOTE Other industry standard 0 6 inch modules may be used as required 6 7 RS 485 COMMUNICATIONS WIRING There are two RS 485 communication ports available on the DE 2200 system Port 2 is for use with an optional Altronic DSM Port 3 is for RS 4...

Страница 8: ...pad which is used to stop reset and test the system The user can also view process information screens view channel specifics cancel timers and view and edit pertinent operating parameters 8 2 STOP The STOP key is used for a manual stop condition By pressing the STOP key the monitor activates the configured output modules in the power supply 8 3 RESET The RESET key clears all past faulted points a...

Страница 9: ... screens used to display several of the most critical operating parameters on one screen All of the home screens provide a status word on the upper line and typically the engine speed on the second line the suction pressure on the third line and the discharge pressure on the fourth line Other analog parameters may be programmed in for the second third and fourth lines The status line will read one...

Страница 10: ...ve timer is set to less than the pre lube timer the display will read RUNNING when the pre lube timer lapses STATUS PRE LUBE SPEED 0 RPM SUCTION 2 3 PSIG DISCHARGE 200 PSIG 9 4 RUNNING After all Class B and Class C points have timed out and are being monitored and if no faults are detected the home screen will show the RUNNING message This is the screen that will remain under normal operation STAT...

Страница 11: ...ws the output switch that is faulted To again view the first fault screen press the VIEW CHAN key If all of the faulted sensors have been cleared and the RESET key is pressed the class B C and output timers will reset and the display will return to the TIMERS ACTIVE home screen STATUS FAULT AL12 1ST FAULT CHAN 24 LOW OIL PRESSURE ESC returns to fault home STATUS FAULT AL12 SPEED 0 RPM SUCTION 102 ...

Страница 12: ...our process screens screens one and three each display up to four user programmed process variables screens two and four display an analog bargraph associated with the previous process variable screen Thus up to eight process variables can be displayed both digitally and in bar graph format The analog values are monitored by a microprocessor on the terminal board and are configured by using a PC a...

Страница 13: ...šššš H then at VIEW press to view next process ESC press To escape 11 0 VIEW CHANNEL STATUS SCREENS 11 1 Use the VIEW CHAN key to enter the view channels screens Once in the VIEW CHAN mode the user can view any channel s details The first line will be the monitor system status TIMERS ACTIVE RUNNING FAULT AL12 or MANUAL STOP The second line shows whether the input point is ARMED or NOT ARMED Class ...

Страница 14: ...the ESC key After five minutes with no keypad activity the display will revert back to the current home screen STATUS TIMERS ACTIVE SPEED 330 RPM SUCTION 102 3 PSIG DISCHARGE 200 PSIG from current home screen VIEW CHAN press STATUS TIMERS ACTIVE NOT ARMED CHAN 10 ENGINE OIL PRESSURE to see channel 20 from channel 10 TENS press STATUS TIMERS ACTIVE ARMED CHAN 20 MANIFOLD PRESSURE to see channel 21 ...

Страница 15: ...by one of the keypad keys RESET or ESC Use VIEW CHAN key to view the status of all channels After all of the current faulted channels are displayed the display will revert back to the first fault If no class A sensors are faulted pressing the RESET key will clear all displayed faults and return the display to the timers active home screen All class B and C input timers and the output timers will b...

Страница 16: ...n the test mode for a preset timed period To enter the test mode make sure the home screen status line says RUNNING and press the TEST key on the keypad The status line will display TEST xxx SEC xxx being the remaining test time To test an input momentarily fault a sensor The display will show the faulted point its description and 1st FAULT for the first point tested To test another point press th...

Страница 17: ...played TEST press test key STATUS TEST 600 SEC SPEED 1000 RPM SUCTION 102 3 PSIG DISCHARGE 200 PSIG No sensors faulted Test home screen is displayed 13 4 To exit the test screen press either the ESC or RESET key Pressing the ESC key takes the user to the STATUS RUNNING home screen and does not reset the class B C and output timers Pressing the RESET key takes the user to the STATUS TIMERS ACTIVE h...

Страница 18: ...ored fault or the activation of the STOP key OUTPUT 4 on the power supply module will be activated and remain activated for the length of the post lube timer Upon the time out of the post lube timer OUTPUT 4 will normalize Pre lube can be aborted by activation of either the CANCEL TIMERS key or the RESET key If the post lube timer is set to zero the system will act as though auto post lube was not...

Страница 19: ... HOURMETER SERVICE MESSAGE NUMBER 600 TOTAL HOURS 8971 RUN TIME HOURS 8 UNITS press to change number HOURMETER SERVICE MESSAGE NUMBER 601 HOURS LEFT 100 CHANGE FILTERS 8 UNITS press to change number Proceed through the servicemeter messages to find the required service The number of hours left until the listed maintenance is due is displayed for each service message There are up to eleven user pro...

Страница 20: ...he values that can be viewed or edited A EDIT SAFETY SHUTDOWN 1 VIEW OR EDIT SETPOINTS Edit analog setpoints 30 46 2 VIEW INPUT CLASS Class A no time delay on start up Class B 10 to 999 seconds time delay on start up before input is active Class C 1 to 999 minutes safe until first met with a global time delay 3 VIEW OR EDIT TEST TIME from 1 to 999 seconds 4 VIEW OR EDIT THE OUTPUT CONFIGURATION N ...

Страница 21: ...lue to be changed ESC The ESC key returns the display back to the previous level of menu screens and when pressed again back to the current home screen 17 4 The menu screens have levels The first level lists the headings of the items to be viewed or edited Upon selecting one of the headings the second level is displayed Press the MENU key to enter the first level of the menu screens The arrow poin...

Страница 22: ...SAFETY SHUTDOWN from main menu Select VIEW INPUT CLASS from next menu EDIT SETPOINTS 6VIEW INPUT CLASS EDIT TEST TIME OUTPUT CONFIG CHAN 610 INPUT CLASS A B C 300 SECONDS TIME DELAY ON START UP Channel 10 s input class configuration will be displayed Each input channel 10 46 can be either class A B or C The class is programmed in the terminal program using the PC Both the high and low setpoints of...

Страница 23: ...ME from the next menu EDIT SETPOINTS VIEW INPUT CLASS 6EDIT TEST TIME OUTPUT CONFIG ENTER press to edit the test time EDIT TEST TIME TEST TIME 6 100 SEC To change the test time use the UNITS or UNITS keys to increase or decrease the value by one Use the TENS or TENS keys to increase or decrease the value by ten The displayed test time is saved when exiting the test time menu The range of the test ...

Страница 24: ... the output will trip following a fault plus the delay time selected This allows for example a delay time between when the fuel valve trips on output 1 and when the ignition shorts on output 2 NEXT press OUTPUT 1 2 3 4 DELAY TIME 2 SEC N O N C IGN ENTER then press A diamond will replace the arrow in front of the selected output switch An arrow will proceed the delay time indicating a change can be...

Страница 25: ...xt output number press the NEXT or TENS or TENS keys until the arrow points to the desired output number and repeat the process 17 9 To view or edit the hourmeter and servicemeter messages select HOURMETER FUNCTIONS from the main menu and press ENTER EDIT SAFETY SHUTDOWN 6HOURMETER FUNCTIONS COMMUNICATIONS NEXT MENU ENTER press to edit hour meter functions HOURMETER SERVICE MESSAGE NUMBER 600 TOTA...

Страница 26: ...To view or edit the time and date select NEXT MENU from the main menu Then select EDIT TIME AND DATE EDIT TIME AND DATE VIEW FIRMWARE REV PREVIOUS MENU from ENTER press The time and date will be displayed with the selection arrow pointing to the time The hours and minutes can be edited separately AM and PM follow the minutes With the selection arrow pointing to the hours use the UNITS or UNITS key...

Страница 27: ...ection arrow will point to the day Use the same procedure to edit the day and the year TIME 11 30 AM DATE 03 25 2001 17 12 To view the firmware revisions of the DISPLAY and TERMINAL modules select NEXT MENU from the main menu then press ENTER EDIT TIME AND DATE 6VIEW FIRMWARE REV PREVIOUS MENU DE 2200 DISPLAY 1 0 0 TERMINAL 1 0 0 NOTE Special firmware versions will display file reference number on...

Страница 28: ...ometer clockwise to lighten the contrast ratio or counterclockwise to darken the contrast ratio To set the potentiometer back to the factory setting with the Display Module at an ambient temperature of approximately 65EF to 77EF 18EC to 25EC turn the potentiometer clockwise until the display contrast ratio is almost too light to read Turn the potentiometer counterclockwise 3 to 3 1 2 turns The dis...

Страница 29: ...mand is shown below The hexadecimal values for the characters are shown only for those using low level assembly language decoding and will not appear on the communications terminal screen ASCII 01 DL 001 HEX 3Eh 28h 30h 32h 20h 44h 4Ch 20h 30h 30h 32h 29h COMMAND HEADER 3Eh The command must begin with the command header START OF TEXT 28h The start of text character must be next NODE NUMBER 01 99 T...

Страница 30: ...og channel value USER LABEL 13th Analog channel value USER LABEL 14th Analog channel value 1ST FAULT HIGH First fault indication when fault occurs CHAN A3 500 PSI Channel number and value of first fault HIGH INTRSTAGE PRESS 20 character label associated with the first fault 10 19 1998 9 46 AM Date and time of the first fault If a view process screen line is not programmed in the monitor the line w...

Страница 31: ...supports register reads data is duplicated for the 30000 s 40000 s address range Maximum number of registers that can be read at one time has been limited to 32 See the Modbus address list at pages 35 36 Note the first 8 Modbus registers duplicate the registers of the Altronic DD 40NTS to simplify user software requirements if both types of systems are in use 20 13 IDENTIFICATION In addition to th...

Страница 32: ...ay is known at both locations Query NN 20 KP CRC CRC Where NN node number 20 KP function code KP is the single byte Key Press from the table below CRC CRC two byte Modbus RTU CRC Key Press Table 00 NONE no keypress returns current display 01 CANCEL TIMERS 02 TEST 03 RESET 04 STOP 05 VIEW 06 NEXT 07 UP UNITS 08 VIEW CHAN 09 F1 10 RIGHT TENS 11 ENTER 12 LEFT TENS 13 F2 14 MENU 15 DOWN UNITS 16 ESC R...

Страница 33: ...uration as profile 0 in nonvolatile memory W0 Use modem profile 0 Y0 store up to four telephone numbers in nonvolatile memory Zn x n is the memory location x is the phone number to be stored For more information on configuring the modem please see the programming instructions Also please refer to the modems user s guide and reference manual 21 4 Upon a fault the monitor sends the dial string to di...

Страница 34: ...tential for normally open sensors that use the engine block as a return path Use an ohmmeter and measure between the power supply minus terminal and the panel and engine block this reading should be less than 2 ohms 22 3 The output LED s are changing state but the relays or solenoid valves connected to the outputs are not tripping A Check that the wiring is correct and check the output module fuse...

Страница 35: ...1 analog value 9999 to 9999 40061 Optional DSM CHAN 12 analog value 9999 to 9999 40062 Optional DSM CHAN 13 analog value 9999 to 9999 40063 Optional DSM CHAN 14 analog value 9999 to 9999 40064 Optional DSM CHAN 15 analog value 9999 to 9999 40065 Optional DSM CHAN 16 analog value 9999 to 9999 40066 Optional DSM CHAN 17 analog value 9999 to 9999 40067 Optional DSM CHAN 18 analog value 9999 to 9999 4...

Страница 36: ... 9999 to 9999 40103 Analog value CHAN 33 9999 to 9999 40104 Analog value CHAN 34 9999 to 9999 40105 Analog value CHAN 35 9999 to 9999 40106 Analog value CHAN 36 9999 to 9999 40107 Analog value CHAN 37 9999 to 9999 40108 Analog value CHAN 40 9999 to 9999 40109 Analog value CHAN 41 9999 to 9999 40110 Analog value CHAN 42 9999 to 9999 40111 Analog value CHAN 43 9999 to 9999 40112 Analog value CHAN 44...

Страница 37: ...S SCREENS 11 0 VIEW CHANNEL SCREENS 12 0 SHUTDOWN OR FAULT STATUS SCREENS 13 0 TEST MODE SCREENS 14 0 AUTO PRE LUBE POST LUBE 15 0 SPEED SWITCH 16 0 THE HOURMETER AND SERVICE METER 17 0 VIEWING OR EDITING THE CONFIGURATION USING THE MENU MODE 18 0 VIEWING THE TIME AND DATE OF THE FIRST FAULT 19 0 CONTRAST RATIO ADJUSTMENT 20 0 DATA LOGGING AND COMMUNICATION OPTIONS 21 0 AUTOMATIC CALL OUT OPTION 2...

Страница 38: ...RAM GENERAL HOOK UP WIRING DIAGRAM SENSOR TRANSDUCER AND THERMOCOUPLE INPUTS WIRING DIAGRAM POWER SUPPLY MODULE WIRING DIAGRAM TACHOMETER INPUT POWER SUPPLY LED AND OUTPUT MODULE LOCATIONS WIRING DIAGRAM RS 485 COMMUNICATIONS WIRING DIAGRAM PERSONAL COMPUTER CONTRAST ADJUSTMENT AND MEMORY LOCATION WIRING DIAGRAM EXTERNAL MODEM ...

Страница 39: ......

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ......

Страница 49: ......

Отзывы: