-16-
12.2 When a fault occurs on an analog channel 30-46, a “HIGH” or “LOW” indication will
additionally be displayed as to whether the point faulted on a high or low setpoint.
STATUS FAULT AL12
1st FAULT HIGH
CHAN 42 300
E
F
HIGH DISCHARGE TEMP
A high setpoint faulted
on an analog input. The
analog value and
“HIGH” are displayed.
RESET
press
reset to
clear fault
13.0 TEST MODE SCREENS
WARNING: TEST MODE DISARMS ALL OUTPUTS. ACTUAL FAULTS WILL DISPLAY BUT
WILL NOT TRIP THE SYSTEM ALARM AND SHUTDOWN OUTPUTS. USE
MANUAL STOP FOR EMERGENCY SHUTDOWN.
13.1 The test mode is used for testing sensors without tripping the outputs. The monitor system
stays in the test mode for a preset timed period. To enter the test mode, make sure the home
screen status line says “RUNNING”, and press the TEST key on the keypad. The status line
will display “TEST xxx SEC”; xxx being the remaining test time. To test an input, momentarily
fault a sensor. The display will show the faulted point, its description and “1st FAULT” for the
first point tested. To test another point press the TEST key, this will clear the tested sensor
from the display and will refresh the test timer to its full programmed test time.
TEST
press to
enter test
mode
STATUS TEST 600 SEC
SPEED 1000 RPM
SUCTION 102 PSIG
DISCHARGE 200 PSIG
Test screen is shown
with no faulted points.
Test key was pressed
from the “RUNNING”
home screen.
STATUS TEST 525 SEC
1st FAULT
CHAN 24
LIQUID LEVEL STAGE 1
sensor point 24 is
tested.
TEST
press
to test
another
sensor