-17-
13.2 When any of the analog channels 30-46 are tested, a “HIGH” or “LOW” indication will
additionally be displayed indicating whether a high or low setpoint was tested. The display
will show the current analog value for the channel selected.
STATUS TEST 530 SEC
1st FAULT HIGH
CHAN 33 5 PSIG
HIGH FILTER PRESS
A high setpoint was
faulted on an analog
input
13.3 If no sensors are faulted and the TEST key is pressed, the display will return to the test home
screen. The test timer will be reset and the home screen parameters and values will be
displayed.
TEST
press
test key
STATUS TEST 600 SEC
SPEED 1000 RPM
SUCTION 102.3 PSIG
DISCHARGE 200 PSIG
No sensors faulted.
Test home screen is
displayed.
13.4 To exit the test screen, press either the ESC or RESET key. Pressing the ESC key takes the
user to the “STATUS RUNNING” home screen and does not reset the class B, C and output
timers. Pressing the RESET key takes the user to the “STATUS TIMERS ACTIVE” home
screen with the class B, C and output timers reset.
ESC
press
esc key
STATUS RUNNING
SPEED 1000 RPM
SUCTION 102.3 PSIG
DISCHARGE 200 PSIG
No sensors faulted.
Running home screen is
displayed.
RESET
press
reset key
STATUS TIMERS ACTIVE
SPEED 1000 RPM
SUCTION 102.3 PSIG
DISCHARGE 200 PSIG
No sensors faulted.
Timers active home
screen is displayed.