14 Technical Specifications
P50 Agile P15D
14-6
P15D/EN TM/B
For operating Time
IDMT Characteristic shape with Relay
Power ON condition
as per class5 of 60255-151 cl.5.2 or
± 60 ms whichever is greater
*(Under reference Condition)
DT Operation
with Relay Power ON condition
± 5% or ± 60 ms whichever is greater**
IDMT characteristic shape
with Relay Power OFF condition
as per class5 of 60255-151 cl.5.2 or
± 90 ms whichever is greater *
(Under reference Condition)
DT Operation
with Relay Power OFF condition
± 5% or ± 90 ms whichever is greater **
Typical Operation Time with auxiliary
supply ON
<= 60 mS
(protection time-delay set to 0 ms; the
injection current is greater than two times
the setting value) The P15D is supplied
from auxiliary supply or pre fault current is
above 0.2 In.
Operating time when Relay is self-powered
and breaker is operated with SOTF
condition
<= 80mS
(protection time-delay set to 0 ms; the
injection current is greater than two times of
the setting value and above In) The pre-
fault current is zero and there is no auxiliary
supply. The case: CB switches on to fault
without auxiliary voltage supply.
*Reference Condition
TMS=1 , I>setting of 1A ,Operating range
2-20 In
** Reference Condition
Fault current 1.5 times above set value
Under current function
(For proper operation, relay must be Powered ON by external auxiliary supply)
II.
For operating value
Pick-up
Below 0.20 In : 0.95 x settings ± 7.50%
Above 0.20 In : 0.95 x settings ± 5%
Drop –off
Below 0.20 In : 1.05 x settings ± 7.50%
Above 0.20 In : 1.05 x settings ± 5%
For operating time
DT Operation
± 5% or ± 60 ms whichever is greater
III.
Thermal Overload function
For operating Time
Thermal Trip operation
± 10% of calculated time
IV.
Cold Load Pickup function
tcold operating Time
tcold
Setting ± 10%
tclp operating Time
tclp
Setting ± 10%
For operating Value
Pick-up
S10% / - 5%
Minimum Trip Level of IDMT
1.05 x Settings ± 5%
Drop –off
0.95 x settings ± 5%
Содержание MiCOM P50 Agile P15D
Страница 2: ......
Страница 3: ...P50 Agile P15D 1 Introduction P15D EN TM B 1 1 INTRODUCTION CHAPTER 1...
Страница 4: ...1 Introduction P50 Agile P15D 1 2 P15D EN TM B...
Страница 8: ...1 Introduction P50 Agile P15D 1 6 P15D EN TM B 2 3 Ordering information Figure 1 Ordering Information...
Страница 9: ...SAFETY INFORMATION CHAPTER 2...
Страница 10: ...Safety Information Pxxx 2...
Страница 21: ...P50 Agile P15D 3 Hardware Design P15D EN TM B 3 1 HARDWARE DESIGN CHAPTER 3...
Страница 22: ...3 Hardware Design P50 Agile P15D 3 2 P15D EN TM B...
Страница 28: ...3 Hardware Design P50 Agile P15D 3 8 P15D EN TM B...
Страница 29: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 1 FRONT PANEL CHAPTER 4...
Страница 30: ...4 Front Panel P50 Agile P15D 4 2 P15D EN TM B...
Страница 35: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 7 Figure 2 USB Port...
Страница 36: ...4 Front Panel P50 Agile P15D 4 8 P15D EN TM B...
Страница 37: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 1 CONFIGURATION CHAPTER 5...
Страница 38: ...5 Configuration P50 Agile P15D 5 2 P15D EN TM B...
Страница 129: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 93 2 4 18 2 View Error Log V00405 VIEW RECORDS Error Log 000 Fault Record...
Страница 130: ...5 Configuration P50 Agile P15D 5 94 P15D EN TM B...
Страница 131: ...P50 Agile P15D 6 Protection Functions P15D EN TM B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Страница 132: ...6 Protection Functions P50 Agile P15D 6 2 P15D EN TM B...
Страница 141: ...P50 Agile P15D 7 Protection Parametre Settings P15D EN TM B 7 1 PROTECTION PARAMETRE SETTINGS CHAPTER 7...
Страница 142: ...7 Protection Parametre Settings P50 Agile P15D 7 2 P15D EN TM B...
Страница 154: ...7 Protection Parametre Settings P50 Agile P15D 7 14 P15D EN TM B...
Страница 155: ...P50 Agile P15D 8 Monitoring Control P15D EN TM B 8 1 MONITORING CONTROL CHAPTER 8...
Страница 156: ...8 Monitoring Control P50 Agile P15D 8 2 P15D EN TM B...
Страница 162: ...8 Monitoring Control P50 Agile P15D 8 8 P15D EN TM B...
Страница 163: ...P50 Agile P15D 9 External Battery Backup P15D EN TM B 9 1 EXTERNAL BATTERY BACKUP CHAPTER 9...
Страница 164: ...9 External Battery Backup P50 Agile P15D 9 2 P15D EN TM B...
Страница 167: ...P50 Agile P15D 10 Impulse Output for Tripping Coil P15D EN TM B 10 1 IMPULSE OUTPUT FOR TRIPPING COIL CHAPTER 10...
Страница 168: ...10 Impulse Output for Tripping Coil P50 Agile P15D 10 2 P15D EN TM B...
Страница 171: ...P50 Agile P15D 11 Impulse for Flag Indicator P15D EN TM B 11 1 IMPULSE FOR FLAG INDICATOR CHAPTER 11...
Страница 172: ...11 Impulse for Flag Indicator P50 Agile P15D 11 2 P15D EN TM B...
Страница 175: ...P50 Agile P15D 12 SCADA Communications P15D EN TM B 12 1 SCADA COMMUNICATIONS CHAPTER 12...
Страница 176: ...12 SCADA Communications P50 Agile P15D 12 2 P15D EN TM B...
Страница 187: ...P50 Agile P15D 13 Installation P15D EN TM B 13 1 INSTALLATION CHAPTER 13...
Страница 188: ...13 Installation P50 Agile P15D 13 2 P15D EN TM B...
Страница 206: ...13 Installation P50 Agile P15D 13 20 P15D EN TM B...
Страница 207: ...P50 Agile P15D 14 Technical Specifications P15D EN TM B 14 1 TECHNICAL SPECIFICATIONS CHAPTER 14...
Страница 208: ...14 Technical Specifications P50 Agile P15D 14 2 P15D EN TM B...
Страница 219: ...P50 Agile P15D 15 Wiring Diagrams P15D EN TM B 15 1 WIRING DIAGRAMS CHAPTER 15...
Страница 220: ...15 Wiring Diagrams P50 Agile P15D 15 2 P15D EN TM B...
Страница 223: ......