P50 Agile P15D
13 Installation
P15D/EN TM/B
13-19
Cleaning
Warning: Before cleaning the IED, ensure that all AC and DC supplies
and transformer connections are isolated to prevent any
chance of an electric shock while cleaning.
Only clean the equipment with a lint-free cloth dampened with clean water. Do not use detergents,
solvents or abrasive cleaners as they may damage the product's surfaces and leave a conductive
residue.
2.4
Troubleshooting
The relay continuously monitors the hardware and detects any hardware fault/error. In case of
hardware failure relay displays the corresponding error code on the LCD. These faults errors are
stored in the error log file and can be viewed from “Error Log” menu. Error log is stored in 16 bit
integer. The bit definition applicable to P15D is as under:
Bit 10 -
15
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Unused
Unused
Fram 3
Error
Unused
Fram 2
Error
Fram 1
Error
ADC
Error
Unused
RTC Error
Unused
Setting
Error
Error code descriptions are given below:
Sr. No
Error Log
Display
Error Data
Bitwise
Description
Causes
Action taken
MCU
Proposed action
1
1
0000 0000
0000 0001
SETTING ERROR
1.
Setting
corrupted
2.
Change in
address of
setting in
memory
ON LED Blinks with 1
sec interval indicating
IED is OUT OF
SERVICE
Go to
CONFIGURATION
menu and restore
default all settings and
then save settings
.Press (RESET +
PROT. RESET).
2
4
0000 0000
0000 0100
RTC ERROR
1.
I2C Bus Error
2.
Damaged RTC
3.
Battery backup
not functioning
Error is checked
periodically after 1
minute interval.
Set correct values for
Date and Time and
Press (RESET +
PROT. RESET).
3
16
0000 0000
0001 0000
ADC ERROR
1.
ADC device not
working.
2.
SPI bus error
ON LED blinks with 1
sec interval indicating
IED is OUT OF
SERVICE
Press (RESET +
PROT. RESET)
4
32
0000 0000
0010 0000
Fram 1 Error
1.
SPI bus error
2.
Fram not
working
Error is checked
periodically after 1
minute interval.
Press (RESET +
PROT. RESET)
5
64
0000 0000
0100 0000
Fram 2 Error
1.
SPI bus error
2.
Fram not
working
Error is checked
periodically after 1
minute interval.
Press (RESET +
PROT. RESET)
6
256
0000 0001
0000 0000
Fram 3 Error
1.
SPI bus error
2.
Fram not
working
Error is checked
periodically after 1
minute interval.
Press (RESET +
PROT. RESET)
Содержание MiCOM P50 Agile P15D
Страница 2: ......
Страница 3: ...P50 Agile P15D 1 Introduction P15D EN TM B 1 1 INTRODUCTION CHAPTER 1...
Страница 4: ...1 Introduction P50 Agile P15D 1 2 P15D EN TM B...
Страница 8: ...1 Introduction P50 Agile P15D 1 6 P15D EN TM B 2 3 Ordering information Figure 1 Ordering Information...
Страница 9: ...SAFETY INFORMATION CHAPTER 2...
Страница 10: ...Safety Information Pxxx 2...
Страница 21: ...P50 Agile P15D 3 Hardware Design P15D EN TM B 3 1 HARDWARE DESIGN CHAPTER 3...
Страница 22: ...3 Hardware Design P50 Agile P15D 3 2 P15D EN TM B...
Страница 28: ...3 Hardware Design P50 Agile P15D 3 8 P15D EN TM B...
Страница 29: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 1 FRONT PANEL CHAPTER 4...
Страница 30: ...4 Front Panel P50 Agile P15D 4 2 P15D EN TM B...
Страница 35: ...P50 Agile P15D 4 Front Panel P15D EN TM B 4 7 Figure 2 USB Port...
Страница 36: ...4 Front Panel P50 Agile P15D 4 8 P15D EN TM B...
Страница 37: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 1 CONFIGURATION CHAPTER 5...
Страница 38: ...5 Configuration P50 Agile P15D 5 2 P15D EN TM B...
Страница 129: ...P50 Agile P15D 5 Configuration P15D EN TM B 5 93 2 4 18 2 View Error Log V00405 VIEW RECORDS Error Log 000 Fault Record...
Страница 130: ...5 Configuration P50 Agile P15D 5 94 P15D EN TM B...
Страница 131: ...P50 Agile P15D 6 Protection Functions P15D EN TM B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Страница 132: ...6 Protection Functions P50 Agile P15D 6 2 P15D EN TM B...
Страница 141: ...P50 Agile P15D 7 Protection Parametre Settings P15D EN TM B 7 1 PROTECTION PARAMETRE SETTINGS CHAPTER 7...
Страница 142: ...7 Protection Parametre Settings P50 Agile P15D 7 2 P15D EN TM B...
Страница 154: ...7 Protection Parametre Settings P50 Agile P15D 7 14 P15D EN TM B...
Страница 155: ...P50 Agile P15D 8 Monitoring Control P15D EN TM B 8 1 MONITORING CONTROL CHAPTER 8...
Страница 156: ...8 Monitoring Control P50 Agile P15D 8 2 P15D EN TM B...
Страница 162: ...8 Monitoring Control P50 Agile P15D 8 8 P15D EN TM B...
Страница 163: ...P50 Agile P15D 9 External Battery Backup P15D EN TM B 9 1 EXTERNAL BATTERY BACKUP CHAPTER 9...
Страница 164: ...9 External Battery Backup P50 Agile P15D 9 2 P15D EN TM B...
Страница 167: ...P50 Agile P15D 10 Impulse Output for Tripping Coil P15D EN TM B 10 1 IMPULSE OUTPUT FOR TRIPPING COIL CHAPTER 10...
Страница 168: ...10 Impulse Output for Tripping Coil P50 Agile P15D 10 2 P15D EN TM B...
Страница 171: ...P50 Agile P15D 11 Impulse for Flag Indicator P15D EN TM B 11 1 IMPULSE FOR FLAG INDICATOR CHAPTER 11...
Страница 172: ...11 Impulse for Flag Indicator P50 Agile P15D 11 2 P15D EN TM B...
Страница 175: ...P50 Agile P15D 12 SCADA Communications P15D EN TM B 12 1 SCADA COMMUNICATIONS CHAPTER 12...
Страница 176: ...12 SCADA Communications P50 Agile P15D 12 2 P15D EN TM B...
Страница 187: ...P50 Agile P15D 13 Installation P15D EN TM B 13 1 INSTALLATION CHAPTER 13...
Страница 188: ...13 Installation P50 Agile P15D 13 2 P15D EN TM B...
Страница 206: ...13 Installation P50 Agile P15D 13 20 P15D EN TM B...
Страница 207: ...P50 Agile P15D 14 Technical Specifications P15D EN TM B 14 1 TECHNICAL SPECIFICATIONS CHAPTER 14...
Страница 208: ...14 Technical Specifications P50 Agile P15D 14 2 P15D EN TM B...
Страница 219: ...P50 Agile P15D 15 Wiring Diagrams P15D EN TM B 15 1 WIRING DIAGRAMS CHAPTER 15...
Страница 220: ...15 Wiring Diagrams P50 Agile P15D 15 2 P15D EN TM B...
Страница 223: ......