.4.4
Check Drainage
DC Inverter Free match Series Cassette Type Unit
.5
Installing the Front Panel
After the pipeline work is finished, check whether the drainage can go
smoothly.
Outdoor unit connection
N(1)
2
3
green
Single-phase units(~24k)
blue
black
brown yellow-
(1) Add slowly about 1L of water into the water tray. After the electric circuit is
completed, check the drainage condition during refrigerating operation.
(1) Temporarily hang the 4 fasteners on the corresponding hooks of the main
body of the indoor unit (Do not let the conducting wires get involved into the
panel will rise).
sealing material).
(2) Screw in the hexagon screws beneath the 4 fasteners by about 15mm (Front
As shown below, take off the 4 corner covers from the front panel and loose the
hexagon screw bolts on the 4 fasteners to the maximum. The position marked with
“PIPING SIDE” on the front panel will direct right at the pipe mouth of the indoor
unit.
(3) As shown below, turn the front panel according to the arrow direction so that
the front panel can be well connected with the ceiling.