AlpicAir ACCMI-26HRDC1A Скачать руководство пользователя страница 24

1

Fig.13

.2.4 Connecting the Pipe at the Outdoor Side Unit

connector. The tightening method is the same as that as at the indoor 

side.

.2.5 Checking the Pipe Connections for Gas Leaking

For both indoor and outdoor unit side, check the joints for gas 

leaking by the use o

f a gas leakage detector without fail when the pipes 

are connected.

.2.6 Heat Insulation on the Pipe Joints (Indoor Side Only)

Stick coupler heat insulation (large and small) to the place where connecting pipes.

Fig.14

.2.7 Liquid Pipe and Drain Pipe

If the outdoor unit is installed lower than 

the indoor unit (See Fig.15)

(1). A drain pipe should be above ground 

and the end of the pipe does not dip into 

water. All pipes must be restrained to the 

wall by saddles.

(2).  Taping pipes must be done from bottom 

to top.

(3).  All pipes are bound together by tape and 

restrained to wall by saddles.

Sealed

Drain
pipe

Saddle

Fig.15

DC Inverter Free match Series Cassette Type Unit

Содержание ACCMI-26HRDC1A

Страница 1: ...Thank you for choosing our product Please read this Owner s Manual carefully before operation and retain it for future reference Owner s Manual Original Instructions Cassette Type Air Conditioner...

Страница 2: ......

Страница 3: ...ACCMI 26HRDC1A ACCMI 36HRDC1A ACCMI 53HRDC1A ACMI 70HRDC1A...

Страница 4: ...20 6 Installation of Controller 30 5 4 Installation of the Drain Hose 22 5 5 The Panel Installation 25 5 6 Electrical Wiring 27 10 7 Test Running 30 9 Safety operation of flammable refrigerant 36 Spec...

Страница 5: ...e the defrosting process or to clean other than those recommended by the manufacture Should repair be necessary contact your nearest authorized Service Centre Any repairs carried out by unqualified pe...

Страница 6: ...allation manual and the appliance national electrical wiring rules or code of practice Insufficient capacity or incomplete electrical work may cause electrical shock or fire 7 Be sure to use a dedicat...

Страница 7: ...jury 16 Be sure to establish an earth Do not earth the unit to a utility pipe arrester or telephone earth Incomplete earth may cause electrical shock or fire A high surge current from lightning or oth...

Страница 8: ...ette Type Unit Drainage pipe 2 4 5 6 Big handle 7 Liquid Pipe 8 Gas pipe 9 10 Drainage pipe Front Board Connection pipe Wired Controller 11 Indoor Outdoor 2 3 4 7 5 6 1 8 9 10 Air inlet 11 Air outlet...

Страница 9: ...or ambient Clock Operation mode Set time TIMER ON TIMER OFF Turbo mode Send signal Auto mode Cool mode Temp Dry mode Fan mode Heat mode I feel Set fan speed display type 3 1 Buttons on remote controll...

Страница 10: ...ifunction For the functions which the model doesn t have if press the corresponding button on the remote controller the unit will keep the original running status After putting through the power the a...

Страница 11: ...cally swing up down at maximum angle When selecting air condition er is blowing fan at xed position Horizontal Press or button once increase or decr ease set temperature 1 F Holding or button 2s later...

Страница 12: ...function please use remote controller to cancel it initial curve setting value of original factory 2 Adjust and button could change the corresponding setting temperature after adjusted press Turbo bu...

Страница 13: ...justed Under 8 heating function set temperature can t be adjusted Press TURBO button and the remote controller won t send signal Sleep function and 8 heating function can t operate at the same time If...

Страница 14: ...on icon is displayed on remote control ler If you operate the remote controller the icon will blink three times without sending signal to the unit During operation poin t the remote control signal se...

Страница 15: ...of the Installation Location WARNING otherwise the unit would topple or fall off Do not install where there is the danger of combustible gas leakage Children under 10 years old must be supervised not...

Страница 16: ...295 270 09K 09K CAUTION 11 2...

Страница 17: ...12 3 15 5 09K 12 18K 24K 2 4x 3...

Страница 18: ...530 530 In order to make the front panel cover 20mm of the ceiling the distance between the ceiling and the unit should be 35mm or less If the distance between the ceiling and the unit is above 35mm a...

Страница 19: ...14 Unit mm Dimensions Model A B C D E F G 950 24K 870 840 680 780 240 135 For the units 24k Table 5 Fig 3 DC Inverter Series Cassette Type Unit...

Страница 20: ...the unit is installed horizontally at four directions If not the water pump and the 5 1 3 Installing the Suspension Bolts and lower sides of the hoisting stand To prevent the gasket from breaking off...

Страница 21: ...Pipe The water level test must be done after installing the indoor unit to make the unit is horizontal as shown below 4 5 2 1 Flare Processing 1 Cut the connection pipe with the pipe cutter and remov...

Страница 22: ...with tape Fig 11 Pipe Cutter Cutt line Heat insulating pipe CAUTION To prevent breaking of the pipe avoid sharp bends Bend the pipe with a radius of curvature of 150 mm or over If the pipe is bent re...

Страница 23: ...nut and lead to leakage Examine the connection pipe to see if it leaks then take the treatment of heat insulation as shown in the Fig 12 Fig 12 Table Flare nut tightening torque Pipe Diameter inch 1 4...

Страница 24: ...Pipe Joints Indoor Side Only Stick coupler heat insulation large and small to the place where connecting pipes Fig 14 2 7 Liquid Pipe and Drain Pipe If the outdoor unit is installed lower than the ind...

Страница 25: ...tion depends on the unit s capacity generally 15 minutes for the 09K and 12K DC Inverter Free match Series Cassette Type Unit 6 Wait for some time to see if the system pressure can remain unchanged 3...

Страница 26: ...lve assembly to two service ports to quicken the evacuating speed DC Inverter Free match Series Cassette Type Unit 7 Slightly open the liquid valve and let some refrigerant go to the connection pipe t...

Страница 27: ...l to prevent the smell from entering indoors or pouring in and cause property loss or personal injury 5 4 2 Installing the Drain Pipe 1 Insert the drain pipe to the drain outlet of the unit and then t...

Страница 28: ...ach indoor unit Fig 21 6 Install one water trap for each unit 7 Installation of water trap shall consider easy cleaning in the future Fig 21 Fig 22 Fig 23 8 Connection of drainage branch pipe to the s...

Страница 29: ...the indoor unit and tighten it with the clamp supporting brackets at an interval of 1 1 5 m have to withstand additional force Correct 1 100 or more gradient wrong Fig 28 5 The incline of attached dra...

Страница 30: ...y hang the 4 fasteners on the corresponding hooks of the main body of the indoor unit Do not let the conducting wires get involved into the panel will rise sealing material 2 Screw in the hexagon scre...

Страница 31: ...screws until the thickness of the sealing material between the NOTES 1 Improper screw looseness will lead to the following problem 2 After the screws are tightened if there is still a gap between the...

Страница 32: ...andards so that the air conditioner can be operated safely and electric company standards DC Inverter Free match Series Cassette Type Unit Always use a special branch circuit and install a special rec...

Страница 33: ...d wire to form a loop suitable for the terminal screw 4 Shape the loop wire properly place it on the terminal board and tighten securely with the terminal screw using a screwdriver 2 For strand wiring...

Страница 34: ...ors with those of the indoor unit side Erroneous wiring may cause burning of the electric parts clamped electric leakage may occur Always connect the ground wire 4 Electric wiring of indoor unit side...

Страница 35: ...connection cord properly based on the corresponding marks as shown in Fig 39 Ground both the indoor and outdoor units by attaching a ground wire Unit shall be grounded in compliance with the applicabl...

Страница 36: ...uited 11 F2 Indoor evaporator temperature sensor is open short circuited 12 F3 Outdoor ambient temperature sensor is open short circuited 13 F4 Outdoor condenser temperature sensor is open short circu...

Страница 37: ...us 24K 2 Instructions to the Error Indicating Lamps on the Panel of the Cassette Type Unit 12 18K When there is no error the dual 8 nixie tube display the set temperature After receiving the command o...

Страница 38: ...Poor heating effect Control loop is abnormal The set room temperature is too low e g a k a e l t n a r e g i r f e r s i e r e h T The outdoor ambient temperature is lower than 5 C 33 Note After carry...

Страница 39: ...or unit in case of electric shock or fire hazard Do not clean the unit with gasolene benzene thinner polishing powder or liquid insecticide Increase the frequency of cleaning if the unit is installed...

Страница 40: ...ter below 45 C with neutral detergent to clean it Then dry the filter at a cool place NOTICE do not use hot water above 45 C to clean otherwise the filter may be discolored or out of shape Do not dry...

Страница 41: ...e kept during the operation process Check whether there is fire source or potential fire source in the maintenance area The naked flame is prohibited in the maintenance area and the no smoking warning...

Страница 42: ...rant filling appliances specialized for R32 Make sure that different kinds of refrigerant won t contaminate with each other After filling is finished please do the leakage detection before test runnin...

Страница 43: ...atmospheres Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants i e non sparking adequately sealed or intrinsi cally safe Presence of fire extingui...

Страница 44: ...nted securely Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of preventing the ingress of flammable atmospheres Replacement parts shall be...

Страница 45: ...n valves on the equipment are closed off k Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked Labelling Equipment shall be labelled sta...

Страница 46: ...erants in recovery units and especially not in cylinders If compressors or compressor oils are to be removed ensure that they have been evacuated to an acceptable level to make certain that flammable...

Страница 47: ......

Страница 48: ...66129937831...

Отзывы: