Tri Power X33 TE 10/20/30/40/60 kVA
27
Recommended Size of Cables
Capacity
Mains Input
(1)
Output/ Bypass Input
(1)
External Battery
(1)
R/S/T/N
PE
R/S/T/N
(2)
PE
+/-/N
PE
10kVA
5 mm
2
3 mm
2
5 mm
2
3 mm
2
8 mm
2
3 mm
2
20kVA
8 mm
2
5 mm
2
6 mm
2
5 mm
2
16 mm
2
8 mm
2
30kVA
16 mm
2
8 mm
2
13 mm
2
8 mm
2
30 mm
2
10 mm
2
40kVA
25 mm
2
10 mm
2
20 mm
2
10 mm
2
50 mm
2
16 mm
2
60kVA
40 mm
2
16 mm
2
35 mm
2
16 mm
2
70 mm
2
25 mm
2
(1)
The recommended maximum length of cabling is less than 10meters.
(2)
Please over size neutral line N by 1.7 times of the phase line for non-linear loads.
Recommended Circuit Breaker Size
Input/ Output
Voltage
Output Power
Mains Input
(1)
Output/Bypass Input
(1)
380 V
10kVA/10KW
30 A
25 A
20kVA/20KW
65 A
50 A
30kVA/30KW
95 A
80 A
40kVA/40KW
125 A
105 A
60kVA/60KW
185 A
160 A
400 V
10kVA/10KW
30 A
25 A
20kVA/20KW
60 A
50 A
30kVA/30KW
90 A
75 A
40kVA/40KW
120 A
100 A
60kVA/60KW
175 A
150 A
415 V
10kVA/10KW
30 A
25 A
20kVA/20KW
55 A
50 A
30kVA/30KW
85 A
70 A
40kVA/40KW
115 A
95 A
60kVA/60KW
170 A
145 A
(1)
T
he sizing takes into account 150% overload capacity.