Tri Power X33 TE 10/20/30/40/60 kVA
44
3-4
Operation Processes
3-4-1
Normal Mode Start-up
(1)
Close UPS Mains Input and Bypass Input Switches.
(2)
Select
→Command→Operation→Normal mode on LCD display. The
UPS will be started and supply output voltage.
(3)
Close UPS Output Switch to supply the power to the load.
3-4-2
Cold Start
(1)
User can start-up UPS by battery when main input power is not
available.
(2)
Select
→Command→Operation→Cold start precharge ready on
LCD display.
(3)
Select Normal mode
to start UPS.
3-4-3
Shutdown
(1)
Select
→Command→Operation→Shutdown on LCD display.
3-4-4
Switch to bypass
(1)
Select
→Command→Operation→Shutdown converter except
bypass on LCD display.
(2)
The Inverter will be shutdown and bypass will supply the power to the load.
If the battery is disconnected, Rectifier and Charger will be shutdown as
well.