Tri Power X33 TE 10/20/30/40/60 kVA
53
7.
Technical Specification
Model
X33 TE 10
X33 TE 20
X33 TE 30
X33 TE 40
X33 TE 60
Capacity
10 kVA
20 kVA
30 kVA
40 kVA
60 kVA
Input
Voltage
400V 3 Phase + N
Voltage Tolerance
±20% @100% load
-40% ~-20% @50% load
Frequency
45 ~ 65Hz
Power Factor
≧
0.99
THDi
< 3%
Output
Voltage
380/400/415V 3 Phase + N
Voltage Tolerance
±1% (Static Load)
Frequency
50/60Hz
Frequency Tolerance
±0.01% (free running)
Power Factor
1.0
Crest Factor
3:1
Voltage Harmonic
Distortion
≦
1% with linear load;
≦
3% with distorting load
Overload
110% for 60 minutes, 125% for 10 minutes, 150% for 1 minutes
Parallel
Up to 6 units
Bypass
Voltage
380/400/415V 3 Phase + N
Voltage Tolerance
Preventive range ±10% (Adjustable ±5% ~ ±15%)
Critical range ±25% (Adjustable ±16% ~ ±30%)
Frequency
50/60Hz
Frequency Tolerance
±1Hz / ±3Hz (Selectable)
Battery
Number of batteries
12V 32/34/36/38/40pcs configurable
Max. Charging Current
3.5 A
7 A
10 A
13 A
20A
Common Battery for
Parallel Configuration
Yes
Internal Battery
Available for housing 12V 7/9Ah 40pcs x 2 strings
N.A.
Maximum Efficiency
VFI Mode
>94%
>94%
>95%
>95%
>95%
ECO Mode
>98%
Backup Mode
>93%
>93%
>94%
>94%
>94%