Alpha Intec 50CS
Fig. 1-12 - Right side flue
Easy-Flue 45 mm clamp
Easy-Flue
40 mm clamp
and seal
Front of boiler
Extension clamp
Inner seal joint
Inner seal joint
Flue length (L)
90° bend
Seal joint
CD Easy-Flue
Ensure outer flue duct of Easy-Flue is horizontal
Ensure the flue extension slopes
downwards towards the boiler by a
minimum of 25 - 30 mm per metre
CD Flue extension
Flue sealing
collar
Ensure the inner duct within the terminal
is at the top.
The inner duct must be positioned
to slope towards the boiler
Note:
120
Terminal
20
133
38
End of extension
1.9. FIT PLUME MANAGEMENT
COMPONENTS - (OPTIONAL)
The following procedures detail the options
for management of the exhaust flue gas/plume
emitted from the terminal.
- The terminal supplied with the Easy-Flue can
be altered to divert exhaust flue gas/plume at
an angle.
This can be achieved by simply turning the end
section of the terminal to the desired angle.
- The CD Easy-Flue can be converted to allow the
inner flue duct to be extended so as to position
the terminal in an area where the exhaust flue
gas/plume will not cause a nuisance. This can
be done before or after installation of the flue,
providing there is access to the terminal from
outside.
a. Remove the screws (1 in Fig. 1-13) securing
the terminal and remove the terminal by
pulling it from the flue assembly. Remove the
screw (2 in Fig. 1-13) securing the terminal
end section and remove the end section from
the terminal.
Fig. 1-13
b. Locate a 93° Plume Management bend
into the flue assembly and rotate it to the
direction required.
c. Connect to the 93° bend the required Plume
Management components as detailed and
refer to Fig. 1-14.
Notes:
- The wall support brackets must be used to
secure the Plume Management pipework
to the wall and prevent disconnection of
the 93° bend from the flue assembly or any
other component.
- Each joint must be secured with one of
the screws provided to prevent accidental
disconnection.
- Ensure there is always a slight slope
towards the flue assembly fitted in the
wall and there is no part of the plume
management pipework where condensate/
rain will collect and cause a blockage or any
restriction.
d. Terminate the Plume Management pipework
by fitting the terminal end section (push-fit)
previously removed. Refer to Fig. 1-13.
e. The Plume Management components
available for extending the inner flue duct
are as follows:-
Plume Management 93° bend 60 mm dia.
(each 93° bend equivalent to 1.3 m flue
length)
Plume Management 45° bend 60 mm dia.
(each 45° bend equivalent to 0.9 m flue
length)
Plume Management 1000 mm extension 60
mm dia. (equivalent to 1 m flue length)
60 mm dia. wall bracket
1
1
2