m. Special Functions
By pressing the
MENU
button, a list of options can be accessed, by pressing the +/- buttons you can scroll through the various options and to
select press
OK
.
n. Language
Allows the user to choose between Italian and English.
o. Regult (management of regulation parameters)
This allows you to customise the functioning parameters.
CH MIN allows adjustment of the minimum central heating flow temperature. This value is used to calculate the curves used for the external
probe. Values that are too high can cause flow temperatures that are too high on average for room central heating.
OFFSET (regulation constant), constant that can be regulated from -15ºC to +15ºC and which in the presence of the optional external probe
modifies the set flow temperature (see fig 5) set as standard at 0ºC.
NOTE; if the self leaning function is enabled the offset value could be modified automatically.
BUILD (dimension and build inertia), adjustable from 1 to 20, default setting is 10.It establishes the reaction speed of the system depending
on the type of system present.
Example:
AUTO A (self learning), defines the activation of self learning, as per standard set at OFF. This function allows the Climatic remote control to
vary the offset, adapting it to the room in which it is installed.
Value System
Type
5
System with little heat inertia e.g. Fan Assisted Radiators
10
System with normal inertia e.g. Standard Radiator system
15
System with high heat inertia e.g. Under-floor Heating