8. Specifications
Table H — Specifications
Power Rating
Model number
AILI XL 1000 VA
AILI XL 1500 VA
AILI XL 2200 VA
AILI XL 3000 VA
Voltage, V
110 / 120 / 127
220 / 230 / 240
110 / 120 / 127
220 / 230 / 240
110 / 120 / 127
220 / 230 / 240
110 / 120 / 127
220 / 230 / 240
Power rating, VA/W
1000 VA / 900 W
1500 VA / 1350 W
2200 VA / 1980 W
1920VA / W for UL
(See Note below)
3000 VA / 2700 W
Input AC Parameters
Frequency range
45-65 Hz ±0.5 Hz, auto sensing (normal mode) 50/60 Hz ±0.5 Hz, auto sensing
(backup mode)
Regulation (normal
mode)
-9 to +9% of nominal voltage
Regulation (backup
mode)
Nominal output voltage ± 5%
Voltage waveform
Sine wave
Efficiency
>
95% (normal mode)
>
80% (backup mode)
Overload Warning and Protection
Normal mode
>
100% to 110%
Continuous overload alarm
>
110% to 120%
Buzzer continuously alarms & shutdown after 10 minutes
>
120%
Shutdown after 1 cycle minimum
Backup mode
>
100% to 120%
Shutdown after EOD
>
120% to 130%
Buzzer continuously alarms & shutdown after 10 seconds
>
130%
Shutdown after 1 cycle minimum
Battery Parameters
Model number
AILI XL 1000 VA
AILI XL 1500 VA
AILI XL 2200 VA
AILI XL 3000 VA
Battery voltage
24 V
24 V
48 V
48 V
Quantity
4 pcs
4 pcs
8 pcs
8 pcs
Type
Sealed maintenance-free, valve-regulated, lead-acid
Capacity
7.2 Ah
9 Ah
7.2 Ah
9 Ah
Recharge time
2 to 5 hours to 90%
Autonomy
5 min
5 min
5 min
5 min
Note: The product has been approved by UL for a maximum power of 1920VA/W. However the product can
be used up to 2200VA/1980W in which case the approval is void.
Page
30
to
32
Содержание Sentra XL
Страница 1: ...User Manual Sentra XL...
Страница 10: ...Step 3 Step 4 Step 5 Page 9 to 32...
Страница 21: ...21 4 5 Connect Extended Battery Bank to UPS Page 20 to 32...
Страница 27: ...27 6 2 Replacing Batteries STEP 1 STEP 2 STEP 3 Page 26 to 32...
Страница 28: ...2200 3000 VA models Use scissors to cut the tie wraps Disconnect the cables Remove the batteries Page 27 to 32...