5. Operation

5.1  Switching On the UPS 

1.

Connect the UPS to the wall receptacle. The LCD displays OFF, when the utility power is normal. If the LCD

is blank, go to step 3.

2.

Press and hold the on button on the front panel for approximately 3 seconds until the buzzer sounds, then

release the on button. The UPS starts and both the LCD and the utility LED (Green) illuminate. The start-up

procedure is complete and the loads are supplied by the UPS..

3.

To cold start the UPS, press and hold the on button on the front panel for approximately 3 seconds until the

LCD illuminates and the buzzer sounds, then release the on button. The UPS starts and the battery backup

LED (amber) illuminates. The cold start-up procedure is complete and the loads are supplied by the UPS.

4.

The UPS runs in backup mode and the buzzer sounds every 2 seconds if there is a power outage or an

over/under voltage. When utility power is restored, the UPS runs in utility mode and the buzzer is silenced.

5.2  Switching Off the UPS 

1.

Press and hold  the off button for at least 3 seconds to switch off the UPS. If you press the off button less

than 3 seconds, the UPS does not execute the shutdown command.

2.

In some cases, the UPS will switch itself off because of an overload, an output short-circuit, or a battery

cutoff point reached in the backup mode.

3.

The UPS automatically switches off the output, beeps for 5 seconds, then completely switches off.

5.3  Plug-in Charge 

1.

If the input power cord is properly connected to the wall receptacle and the utility power is normal, the

UPS automatically starts charging the batteries without processing the switch on procedure.

2.

If the UPS isn't used for extended periods, charge the batteries for at least 8 hours every 3 months to

prevent the batteries from becoming discharged. The batteries will slowly discharge when left idle.

5.4  Auto-Restart 

If the input power cord is properly connected to the wall receptacle and the utility power returns to normal, the UPS 

automatically restarts and provides power to the output from utility. 

5.5  Alarm Silence 

1.

The alarm can be switched off by pressing the on button for approximately 1 second when in backup mode.

2.

Unless other warnings or faults appear, the alarm remains silent after the alarm silence has been switched

off.

Page 

22

 to 

32

Содержание Sentra XL

Страница 1: ...User Manual Sentra XL...

Страница 2: ...4 1 Connect Utility and Load 17 4 2 Connect Network Surge protection 18 4 3 Connect Computer Interface Port 18 4 4 Connect Extended Battery Bank 19 4 5 Connect Extended Battery Bank to UPS 20 4 6 REP...

Страница 3: ...3 7 Communication 28 7 1 DB 9 Connector 28 7 2 Options for Intellislot SNMP Card Optional 29 8 Specifications 30 9 Signalling Circuit Connections 31 10 Warranty and Service Information 32 Page 2 to 32...

Страница 4: ...the UPS Install the UPS away from objects that give off excessive heat and areas that are excessively wet Do not install the UPS in an environment with sparks smoke or gas Not for use in a computer r...

Страница 5: ...ck convertible design a single AVR boost and single buck pure sine wave output a user friendly LCD display a built in customer option slot hot swappable batteries and a USB RS232 communication interfa...

Страница 6: ...se of it properly 3 2 Unpacking 1 Take the UPS out of the PE foam 2 Remove the packing materials 3 A standard unit includes One 1 user manual One 1 AC input power cord not supplied with hard wired mod...

Страница 7: ...s below 1 Ensure there is at least 20 cm 8 inches of clearance between the rear panel of the UPS and the wall or other obstructions 2 Do not block the air flow to the ventilation openings of the unit...

Страница 8: ...tower mount stand alone or rack mount To install the UPS as a tower see Section 3 4 1 For rack mount see Section 3 4 2 3 4 1 Tower Mount Stand Alone Stand alone unit NOTE See Section 3 5 to rotate the...

Страница 9: ...9 3 4 2 Rack Mount Setup Step 1 Step 2 NOTE See Section 3 5 to rotate the LCD display to match the physical orientation of the unit Page 8 to 32...

Страница 10: ...Step 3 Step 4 Step 5 Page 9 to 32...

Страница 11: ...anel The front panel can be rotated to accommodate the orientation of the UPS To position the display to match the physical orientation of the unit pull the display out rotate it and then push it back...

Страница 12: ...ch 5 Battery replacement 6 Battery backup LED 7 Battery low 8 Bypass 9 Utility low UPS boost 10 Utility high UPS buck 11 UPS output indicator 12 Polarity error or ground fault 13 Overload 14 Load batt...

Страница 13: ...Output Circuit Breaker for 6 1000 model only 15A Output Circuit Breaker for 6 1500 model only 6 NEMA 5 15R Output Receptacles 7 Cooling vents 8 12 A input circuit breaker 1000 model only 15 A input ci...

Страница 14: ...ort 4 RS232 DB 9 port 5 1 15 A output circuit breaker for 6 1 5 2 20 A output circuit breaker for 6 2 6 1 NEMA 5 15R output receptacles 6 2 NEMA 5 20R output receptacles 7 Cooling vents 8 30 A input c...

Страница 15: ...circuit breaker for 6 1 5 2 20 A output circuit breaker for 6 2 6 1 NEMA 5 15R output receptacles 6 2 NEMA 5 20R output receptacles 6 3 NEMA 5 30R output receptacles 7 Cooling vents 8 30 A input circu...

Страница 16: ...rcuit breaker for 6 1000 model only 10 A output circuit breaker for 6 1500 mode only 6 IEC 320 C13 output receptacles 7 Cooling vents 8 8 A input circuit breaker 1000 model only 10 A input circuit bre...

Страница 17: ...ation switch 3 USB port 4 RS232 DB 9 port 5 3 10 A output circuit breaker for 6 3 6 3 Output IEC 320 C13 6 4 Input IEC 320 C20 7 Cooling vents 8 Input circuit breaker 9 IEC 320 C20 input socket 10 Ext...

Страница 18: ...series Model AILI XL 3000 to reduce the risk of fire connect only to a circuit provided with 30 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code ANSI...

Страница 19: ...on the rear of the UPS Use a network cable to connect the OUT jack to the network equipment 4 3 Connect Computer Interface Port Use the interface cable RS 232 or USB optional to connect the interface...

Страница 20: ...k with connectors that are a different color from the battery bank connector in the UPS UPS model Nominal system voltage connector color Battery bank model AILI XL 1000 VA 24 VDC red BBC AILI 1000 AIL...

Страница 21: ...21 4 5 Connect Extended Battery Bank to UPS Page 20 to 32...

Страница 22: ...facing with the REPO circuit so that the UPS input feeder breaker can be switched off to interrupt all sources of power to the UPS and connected equipment This must be done to comply with national and...

Страница 23: ...nds to switch off the UPS If you press the off button less than 3 seconds the UPS does not execute the shutdown command 2 In some cases the UPS will switch itself off because of an overload an output...

Страница 24: ...test procedure stops If the batteries are weak or dead the battery replacement symbol on the LCD panel appears steadily CAUTION The UPS will not provide any output power if the start up procedure has...

Страница 25: ...procedure has not completed properly even though the input power cord is connected to the wall receptacle CAUTION The battery is heavy pull the battery out onto flat stable surface CAUTION Do not disc...

Страница 26: ...2 12 VDC 7 0 Ah Toplite Guangzhou Technology Battery Co Ltd MH29104 NPW36 12 12 VDC 7 2 Ah First Power Technology Co Ltd MH28204 FP1270 12 VDC 7 0 Ah Shenzhen Center Power Technology Co Ltd MH25860 CP...

Страница 27: ...27 6 2 Replacing Batteries STEP 1 STEP 2 STEP 3 Page 26 to 32...

Страница 28: ...2200 3000 VA models Use scissors to cut the tie wraps Disconnect the cables Remove the batteries Page 27 to 32...

Страница 29: ...ale connector on the rear panel that allows the UPS to communicate with a computer with UPS software The connection provides serial communications for utility and battery signals Table G DB 9 pin assi...

Страница 30: ...ntellislot SNMP Card Optional When this card is plugged in it enables the user to communicate monitor manage and control the UPS remotely via standard network management protocol SNMP using the intern...

Страница 31: ...kup mode Overload Warning and Protection Normal mode 100 to 110 Continuous overload alarm 110 to 120 Buzzer continuously alarms shutdown after 10 minutes 120 Shutdown after 1 cycle minimum Backup mode...

Страница 32: ...in the following schematic Outlet Relay Switch Line Input K board Input Voltage Sensor Output Current Sensor Output Voltage Sensor Main Transformer D board I board To PC RS232 Port USB Port SNMP Port...

Страница 33: ...cost of shipping the repaired or replacement unit back to the customer Battery Warranty Battery warranty provided by Alpha is a three year full replacement warranty with a pro rated warranty for the f...

Страница 34: ...k energy com France and Benelux fbnl alpha outback energy com Spain spain alpha outback energy com Russia russia alpha outback energy com Africa africa alpha outback energy com Alpha and Outback Energ...

Отзывы: