background image

11

Subject to technical amendments without notice  |  83059700gUK – Translation of the operating manual |  ait-deutschland GmbH

Horizonzal connection

1.  Open break-outs on the right sidewall

2.  Trim  the  4  hoses  (accessories)  to  length  if 

required.  Likewise  the  condensate  hose,  which 
hangs loose from the condensate pan.

3.  Attach the hoses and the condensation hose and 

lead out on the right side.

1

2

5

3

4

1  Desuperheating return
2  Desuperheating supply
3  Heating circuit return

 +HDWLQJFLUFXLWVXSSO\ÀRZ

5  Condensation hose

6.1  Condensate drain

The  condensate  precipitated  from  the  air  must  be 
removed frost-free via a condensate pipe with minimum 
40  mm  diameter.  If  surfaces  are  water  permeable,  it 

LVVXႈFLHQF\IRUWKHFRQGHQVDWHZDWHUSLSHWREHODLG

vertically in the ground to a depth of at least 90 cm. If 
the  condensate  is  discharged  into  the  sewer  system, 
ensure frost-free laying with a gradient.

Discharge  of  the  condensate  into  the  sewers  is 
permitted only via a funnel waste trap, which must be 
accessible at all times.

Observe local regulations!

Electrical installation

Connect the electrical cables

ATTENTION

Irreparable  damage  to  the  compressor  due  to  wrong 

URWDWLQJ¿HOG

 

Ź (QVXUHWKDWWKHUHLVDFORFNZLVHURWDWLQJ¿HOGIRU

the compressor load infeed.

Basic information about the electrical 
connection

 

Ɣ

7KH VSHFL¿FDWLRQV RI WKH ORFDO HQHUJ\ VXSSO\

companies may apply to electrical connections.

 

Ɣ

Fit  the  power  supply  for  the  heat  pump  with  an 
all-pole circuit breaker with at least 3 mm contact 
spacing (acc. to IEC 60947-2). 

 

Ɣ

Note 

the 

level 

of 

the 

tripping 

current 

(

Æ

“Technical  data/Scope  of  supply”  on  page 

17).

 

Ɣ

Comply  with  the  electromagnetic  compatibility 
regulations (EMC regulations).

 

Ɣ

Lay  the  control/sensor  cables  and  device  supply 

FDEOHVXႈFLHQWO\IDUDSDUW!PP

 

Ɣ

Lay unshielded power supply cables and shielded 

FDEOHVEXVFDEOHVXႈFLHQWO\IDUDSDUW

 

Ɣ

Do not lengthen the patch cable or the bus cable. 
Bus  cables  up  to  30 m  long  can  be  used  when 
the quality of the cable is the same as that of the 
original cable.

Electrical connection

Pull  in  the  cables  and  conductors  and  create  the 
connections

1.  Strip  the  sheathing  of  all  cables  to  the  external 

loads before laying in the cable gland of the switch 
box.

2.  Open electrical switch box.

3.  Feed  the  control/sensor  cables  and  unit  supply 

cable into the housing.

4.  Connect  cables  to  the  respective  terminals  (

Æ

 

“Terminal diagram” on page 29).

Содержание LWP Series

Страница 1: ...UK 83059700gUK Translation of the operating manual Air water heat pumps Operating Manual LWP...

Страница 2: ...cope of supply 8 5 2 Storage 8 5 3 Unpacking and transport 8 5 4 Installation 9 5 5 Noise 10 6 Hydraulic installation 12 6 1 Condensate drain 13 7 Electrical installation 14 OXVKLQJ OOLQJ DQG YHQWLQJ...

Страница 3: ...l hydraulic integration Operating manual of the heating and heat pump controller Brief description of the heat pump controller Operating manual of the expansion board Log book 1 3 Symbols and markings...

Страница 4: ...ies and damage to property Ensure that personnel are familiar with local regulations especially those on safe and hazard aware working OORZ TXDOL HG SHUVRQQHO ZLWK HOHFWULFDO WUDLQLQJ only to carry ou...

Страница 5: ...ystems Proper planning design and commissioning Closed system with regard to corrosion Integration of an adequately dimensioned pressure maintaining device Use of demineralised heating water or VDI 20...

Страница 6: ...sides 3 2 Wall mounted controller The box with the wall mounted controller is located at the bottom right in the device 3 3 Layout NOTE This section essentially names the FRPSRQHQWV UHOHYDQW IRU IXO O...

Страница 7: ...is hereby discharged to the heating water and is used in the heating circuit The liquid refrigerant at a high pressure and high temperature is depressurised expansion valve The pressure and temperatur...

Страница 8: ...cutting your hands on sharp edges of the device Wear cut resistant protective gloves The hydraulic connections are not designed for mechanical loads Do not lift or transport the device by the hydraul...

Страница 9: ...ice 2 Dispose of the transport and packaging material in an environmentally friendly way and in accordance with local regulations 5 4 Installation Set up and connection CAUTION In the air outlet area...

Страница 10: ...r unit model 7HFKQLFDO GDWD VFRSH RI VXSSO RYHUYLHZ HDWLQJ FLUFXLW VHFWLRQ RQQHFW WKH XQLW WR WKH HG SLSLQJ RI WKH KHDWLQJ circuit via vibration decouplers You must install them to prevent the transfe...

Страница 11: ...lectrical cables ATTENTION Irreparable damage to the compressor due to wrong URWDWLQJ HOG QVXUH WKDW WKHUH LV D FORFNZLVH URWDWLQJ HOG IRU the compressor load infeed Basic information about the electr...

Страница 12: ...HYHQWLQJ damage in hot water heating systems Required pH value 8 2 10 for aluminium materials pH value 8 2 8 5 Fill the system only with demineralised heating water VE water or VDI 2035 water low salt...

Страница 13: ...or the integration of storage tanks in series Complete the work steps quickly otherwise the maximum return temperature may be exceeded and the heat pump switches to high pressure fault 7XUQ WKH DGMXVW...

Страница 14: ...epartment In other countries Send notice of completion for heat pump systems and rough checklist to the manufacturer s local partner 4 Arrange for the heat pump system to be commissioned by after sale...

Страница 15: ...3 Faults Read out the cause of the fault via the diagnostics program of the heating and heat pump controller Contact the local partner of the manufacturer or the factory s customer service Have the fa...

Страница 16: ...16 Subject to technical amendments without notice 83059700gUK Translation of the operating manual ait deutschland GmbH...

Страница 17: ...nd pressure level at 1 m distance from edge of unit Outside Max dB A Sound power level Inside Max dB A Sound power level Outside Max dB A Sound power level per EN12102 dB A Heat source Air flow rate a...

Страница 18: ...t pump VD Compressor Temp Hot water temperature Flow Return 823279a 10 15 20 25 30 35 40 45 50 55 60 65 70 75 22 17 12 7 2 3 8 13 18 23 28 33 Temp C Qh kW 35 C 1VD 55 C 1VD 35 C 2VD 55 C 2VD 1 2 3 4 5...

Страница 19: ...SDFLW LQGH p Pressure loss heat pump VD Compressor 823279a 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 15 20 25 30 35 40 Temp C Q0 kW 7 C 1VD 18 C 1VD...

Страница 20: ...leranz Allgemein DIN ISO 2768 cL Oberfl chen ArtikelNr Dimensioned drawing LWP Item Name 1 Horizontal connection area water condensate 2 Vertical connection area water condensate feed through electric...

Отзывы: