1 Desuperheater venting
2 Condenser venting
3 Condenser venting
4 Condenser emptying
9
Insulate hydraulic
connections
Insulate hydraulic lines in accordance with local
regulations.
1.
2SHQVKXWRႇGHYLFHV
2. Perform a pressure test and check for leaks.
3. Insulate external piping on site.
4.
,QVXODWHDOOFRQQHFWLRQV¿WWLQJVDQGSLSHV
5. If the device is used for cooling below 18°C, the
LQVXODWLRQPXVWEHYDSRXUGLႇXVLRQWLJKW
6. If desuperheating is used on the device,
the insulation on the corresponding lines
and components must be able to withstand
temperatures up to 90°C.
7. Isolate the cones drain in a frost-proof manner
10
6HWWKHRYHUÀRZYDOYH
NOTE
Ɣ
The activities in this section are only
necessary for the integration of storage
tanks in series .
Ɣ
Complete the work steps quickly, otherwise
the maximum return temperature may be
exceeded and the heat pump switches to
high-pressure fault.
Ɣ 7XUQ WKH DGMXVWLQJ NQRE DW WKH RYHUÀRZ
valve to the right to increase the
WHPSHUDWXUHGLႇHUHQFHWKHVSUHDGWXUQLW
to the left to reduce it.
9
System is running in heating mode (ideally in cold
condition).
1. In case of low heating curve: Set the system to
)RUFHG KHDWLQJ
Æ
operating manual of the
heating and heat pump controller).
2.
6KXWRႇYDOYHVWRWKHKHDWLQJFLUFXLW
3.
(QVXUHWKDWWKHWRWDOÀRZLVURXWHGYLDWKHRYHUÀRZ
valve.
4.
5HDGRXWWKHÀRZDQGUHWXUQWHPSHUDWXUHDWWKH
heating and heat pump controller (
Æ
operating
manual of the heating and heat pump controller).
5.
7XUQWKHDGMXVWLQJNQRERIWKHRYHUÀRZYDOYH
XQWLO WKH VSUHDG EHWZHHQ WKH ÀRZ DQG UHWXUQ
temperature is set as follows:
Outdoor temperature
Recommended
setting
-10 °C
4 K
0 °C
5 K
10 °C
8 K
20 °C
9 K
30 °C
10 K
6. Open valves to heating circuit.
7. Reset the heating and heat pump controller.