22
We reserve the right to modify technical specifications without prior notice.
UK830510/191106
© Alpha-InnoTec GmbH
beginning first on one side and moving upwards,
lock the
screen's snap-in lugs in place
in the slots
provided on the front of the facade...
next, on the opposite side, moving upwards.
lock the screen's snap-in lugs
in place
in the slots
provided on the front of the facade…
finally, press the screen's upper snap-in lugs into
the slots provided on the front of the facade.
removing the sCreen
In order to remove the screen, the snap-in lugs
must
first be loosened by pressing one side
completely
toward the middle of the screen
.
Thereafter, remove the snap-in lugs from the opposite
side.
Commissioning
Danger!
the unit may be commissioned only
with the air ducts and weather grille or
rain guard installed and with the covers
closed.
proceed as follows:
conduct a thorough installation inspection and go
through the items on the general checklist.
“General checklist”.
The installation inspection will prevent damage to
the heat pump system that could be caused by in-
correct installation work.
make sure of the following...
•
Clockwise rotary field
of the load power sup-
ply (compressor).
•
Installation and assembly
of the heat pump ac-
cording to the information in this operating man-
ual.
•
All electric installation work must be properly
completed.
•
A
3-pole automatic circuit-breaker
must be
installed for the compressor. It must have a con-
tact gap of at least 3 mm.
•
The heating circuit must be rinsed, filled and thor-
oughly bled.
•
All valves and shut-off devices of the heating cir-
cuit must be open.
•
All pipe systems and components of the system
must be sealed.
carefully fill out and sign the completion report for
heat pump systems...
“completion report for heat pump systems”.
In Germany:
Send completion report for heat pump systems and
general checklist to the manufacturer’s factory cus-
tomer service department.
outside of Germany:
Send completion report for heat pump systems and
general checklist to the manufacturer’s local part-
ner.
overview “customer service”.