proceed as follows:
Rinse heating circuit thoroughly prior to connecting
the unit to the heating circuit...
notICe.
Contamination and deposits in the heating
circuit can cause malfunctions.
Install shut-off devices for the hot water outflow
(forward flow) and hot water inflow (return flow)
on the heat pump side.
notICe.
During installation of the shut-off devic-
es, the liquefier of the heat pump can be
rinsed, if necessary.
WarnIng!
the condenser may be rinsed only by cus-
tomer service personnel authorized by the
manufacturer.
connect the unit to the pipes of the heating cir-
cuit via vibration decouplers. They must be installed
in order to prevent damage from vibrations to the
pipes.
notICe.
vibration decouplers are available as ac-
cessories.
The connections for the heating water outflow (forward
flow) and the hot water inflow *(return flow) are marked
accordingly.
for positioining of the connections, reference
the dimensional drawing for the respective
model.
Condensate disCharge
The condensation water that accumulated from the air
must be drained via the pre-mounted hose in the unit
for condensate discharge. To do so, connect the hose
for condendate discharge with a water drain.
for positioning of the connection for conden-
sate discharge, see dimensional drawings for the
respective model.
installation / ConneCtion to heating CirCuit
Danger!
Danger of fatal injury due to electric cur-
rent!
Before opening the unit, disconnect the
system from the power supply and secure
it from being switched back on!
CautIon.
Connect the unit to the heating circuit ac-
cording to the hydraulic diagram for the
respective model.
“Hydraulic connection” instructions.
notICe.
Check to make sure that the diameters
and lengths of the pipes for the heating
circuit are sufficiently dimensioned.
notICe.
Circulating pumps must be multi-stage,
regulated pumps. they must be able to de-
liver at least the minimum hot water flow
rate required for your model.
overview “Technical data / scope of delivery”,
“heating circuit” section.
CautIon.
the hydraulic system must be equipped
with a buffer tank, the required volume of
which depends on the model of your unit.
overview “Technical data / scope of delivery”,
“heating circuit, buffer tank” section.
CautIon.
When installing the connections, always
secure the connections on the unit from
twisting, in order to prevent damage to
the copper pipes in the interior of the
unit.