Maintenance and Troubleshooting
92
Error
No.
Error Description
Solution
100042 Output_short
Disconnect the Backup load and restart the
inverter. If the fault can be cleared, then
the load side is shorted; If the fault can't be
cleared, please contact the customer ser-
vice center for further check.
100043 Output_overload
1. The Backup load is overloaded, check
whether the load connected to the backup
terminal exceeds the overload limit, reduce
the load, restart the inverter or wait for 5
minutes to automatically eliminate the
fault;
2. Disconnect the Backup load, restart the
inverter, and check whether the fault is
cleared. If the fault can't be clear, please
contact the customer service center for
further check.
100046 DC_Input_Disturbance
1. If it happens occasionally, the inverter
can recover automatically, no processing is
required.
2. If it persists, please contact the customer
service center for further check.
100052 Backup_ovp
1. If it happens occasionally, the inverter
can recover automatically, no processing is
required.
2. If it persists, please contact the customer
service center for further check.
100054 Dc_bus_undervolt
1. If it happens occasionally, the inverter
can recover automatically, no processing is
required.
2. If it persists, please contact the customer
service center for further check.
Содержание ES-Alpha-Smile 5-10KWH-v2
Страница 1: ...V01 INSTALLATION OPERATION MAINTENANCE MANUAL OF SMILE5 ENERGY STORAGE SYSTEM ESS ...
Страница 2: ......
Страница 68: ...Installer Account Register and Install New System 66 7 1 3 Overview of Functions for Installer Account ...
Страница 111: ...Appendix 1 System Overview 109 13 Appendix 1 System Overview ...
Страница 113: ...Appendix 2 Regional Application Standard 111 ...