![Alpha ESS ES-Alpha-Smile 5-10KWH-v2 Скачать руководство пользователя страница 103](http://html.mh-extra.com/html/alpha-ess/es-alpha-smile-5-10kwh-v2/es-alpha-smile-5-10kwh-v2_installation-operation-and-maintenance-manual_2905569103.webp)
Maintenance and Troubleshooting
101
10.2.2.
Battery Protection Description
LED
Indictor
Protection
Code
LED
Display
Description
Troubleshooting
Green
LEDs
flicker
once
every 3S
.
1
Temperature
difference
Wait for automated
recovery.
In case the problem is not
recovery for a long time, call
for service.
3
High
temperature
Stop discharging and
charging until this code is
eliminated and wait for the
temperature to drop.
4
Low-
temperature
discharge
Stop discharging until this
code is eliminated and wait
for the temperature to rise.
5
Overcurrent
charge
Wait for automated
recovery.
In case the problem is not
recovery for a long time, call
for service.
6
Overcurrent
discharge
8
Cell
overvoltage
9
Cell under
voltage
Stop charging and call
service immediately.
11
Low-
temperature
charge
Stop charging until this code
is eliminated and wait for
the temperature to rise.
In the case of work mode, if the protection code 9 appears, please press the power
button of the battery 5 times within 10 seconds, the BMS will be forced to turn on the
MOSFET of discharge so that the inverter can detect the battery open voltage and
charge the battery.
Содержание ES-Alpha-Smile 5-10KWH-v2
Страница 1: ...V01 INSTALLATION OPERATION MAINTENANCE MANUAL OF SMILE5 ENERGY STORAGE SYSTEM ESS ...
Страница 2: ......
Страница 68: ...Installer Account Register and Install New System 66 7 1 3 Overview of Functions for Installer Account ...
Страница 111: ...Appendix 1 System Overview 109 13 Appendix 1 System Overview ...
Страница 113: ...Appendix 2 Regional Application Standard 111 ...