• Be sure to operate the generator at a rated
frequency, irrespective of the load capacity.
• Operating the unit at a frequency lower than the
rated frequency could result in generator damage.
• Avoid operating the unit for long periods without
loads or with light loads.
To Start Unit
Manual Operation
1. Check and confirm that both the main circuit
breaker (
A
) on the operation panel and the circuit
breakers for the auxiliary receptacles at the output
terminal panel are in the OFF position.
2. Set the selector switch (
B
) to MANUAL operation.
3. Turn the starter switch (
C
) to the RUN position.
The engine starts preheating automatically.
4. When the preheating lamp (
D
) turns off, turn the
starter switch (
C
) to the START position to start
the engine.
5. Once engine has started, let it warm up about 5
minutes at no-load condition.
6. After warm-up, set the engine speed switch (
E
)
to the HIGH position, then adjust the frequency
adjuster (
F
) UP or DOWN until the frequency
meter (
G
) reads 60 Hz.
7. Adjust to the rated voltage by turning the voltage
adjuster knob (
H
) while monitoring the voltmeter
(
I
).
8. Supply power to the load(s) by switching both the
main circuit breaker (
A
) and the circuit breaker(s)
for the auxiliary receptacle(s) to the ON position.
C
B
D
H
A
G
I
F
E
Go
to
Discount-Equipment.com
to
order
your
parts
Содержание Maxi-Power MP65-8B1
Страница 8: ...7 I A H B E G C F D K J G o to Discount Equipm ent com to order your parts ...
Страница 39: ...38 ALLMAND COM Wiring Diagram Generator G o to Discount Equipm ent com to order your parts ...
Страница 40: ...39 Engine G o to Discount Equipm ent com to order your parts ...
Страница 41: ...40 ALLMAND COM G o to Discount Equipm ent com to order your parts ...
Страница 44: ...43 Addendum B Tire Safety Information G o to Discount Equipm ent com to order your parts ...