506887-01
Page 23 of 78
Issue 1213
5.
On field supplied terminations for sidewall exit, exhaust
piping may extend a maximum of 12 inches (305 mm)
for 2” PVC and 20 inches (508 mm) for 3” (76 mm) PVC
beyond the outside wall. Intake piping should be as short
as possible. See Figures 22 and 23.
6.
On field supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of the
intake pipe without a termination elbow is 8” and a
minimum distance of 6” with a termination elbow. See
Figures 22 and 23.
7.
If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other
obstructions, piping must be supported every 24” (610
mm) as shown in Figures 22 and 23. In addition, close
coupled wall termination must be extended for use in
this application. See Figures 22 and 23. When exhaust
and intake piping must be run up an with pipe sized per
Table 7. The intake piping may be equipped with a 90°
elbow turndown. Using turndown will add 5 feet (1.5 m)
to the equivalent length of the pipe.
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
Figure 26
See venting Table 5 for maximum venting lengths with this
arrangement.
* Use wall support every 24” (610 mm). Use two wall supports if
extension is greater than 24” (610 mm) but less than 48” (1219 mm).
NOTE:
One wall support must be 6” (152 mm) from top of each pipe
(intake and exhaust).
FIELD SUPPLIED WALL TERMINATION
with INTAKE ELBOW
Figure 25
EXHAUST PIPE TERMINATION SIZE REDUCTION
Table 7
* 070 and 090 units installed with flush mount termination must use the 1-1/
2” accelerator supplied with the kit.
Содержание A97USMV
Страница 3: ...506887 01 Page 3 of 78 Issue 1213 A97USMV Exploded View Figure 1 ...
Страница 16: ...506887 01 Page 16 of 78 Issue 1213 Figure 17 ...
Страница 28: ...506887 01 Page 28 of 78 Issue 1213 Trap Drain Assembly using 1 2 PVC or 3 4 PVC Figure 38 ...
Страница 35: ...506887 01 Page 35 of 78 Issue 1213 ...
Страница 36: ...506887 01 Page 36 of 78 Issue 1213 Figure 46 ...
Страница 39: ...506887 01 Page 39 of 78 Issue 1213 ...
Страница 40: ...506887 01 Page 40 of 78 Issue 1213 Typical A97USMV Wiring Diagram Figure 47 ...
Страница 41: ...506887 01 Page 41 of 78 Issue 1213 Integrated Control Figure 48 ...
Страница 42: ...506887 01 Page 42 of 78 Issue 1213 Low Voltage Field Wiring Table 14 2 Stage Single Stage ...
Страница 46: ...506887 01 Page 46 of 78 Issue 1213 BLOWER DATA ...
Страница 47: ...506887 01 Page 47 of 78 Issue 1213 BLOWER DATA ...
Страница 48: ...506887 01 Page 48 of 78 Issue 1213 BLOWER DATA ...
Страница 49: ...506887 01 Page 49 of 78 Issue 1213 BLOWER DATA ...
Страница 50: ...506887 01 Page 50 of 78 Issue 1213 BLOWER DATA ...
Страница 51: ...506887 01 Page 51 of 78 Issue 1213 BLOWER DATA ...
Страница 52: ...506887 01 Page 52 of 78 Issue 1213 BLOWER DATA ...
Страница 53: ...506887 01 Page 53 of 78 Issue 1213 BLOWER DATA ...
Страница 54: ...506887 01 Page 54 of 78 Issue 1213 BLOWER DATA ...
Страница 55: ...506887 01 Page 55 of 78 Issue 1213 TABLE 22 ...
Страница 56: ...506887 01 Page 56 of 78 Issue 1213 TABLE 23 ...
Страница 60: ...506887 01 Page 60 of 78 Issue 1213 Figure 50 ...
Страница 68: ...506887 01 Page 68 of 78 Issue 1213 ...
Страница 69: ...506887 01 Page 69 of 78 Issue 1213 ...
Страница 70: ...506887 01 Page 70 of 78 Issue 1213 ...
Страница 75: ...506887 01 Page 75 of 78 Issue 1213 Troubleshooting Cooling Sequence of Operation Call for Cooling ...