background image

506762-01

Page 7  of  24

Issue 1143

Brazing Connection Procedure

1.

Cut ends of refrigerant lines square (free from nicks or
dents).  Debur the ends.   The pipe must remain round;
do not pinch end of line.

2.

Before making line set connections, use dry nitrogen to purge
the refrigerant piping.  This will help to prevent oxidation and
the introduction of moisture into the system.

3.

Use silver alloy brazing rods (5% or 6% silver alloy for
copper-to-copper brazing or 45% silver alloy for copper-
to-brass or copper-to-steel brazing) which are rated for
use with R-410A refrigerant.

4.

Remove the Schrader core assemblies before brazing
to protect them from damage due to extreme heat.
Replace the cores when brazing is complete.

5.

Remove light maroon washers from service valves and
shield light maroon stickers to protect them during brazing.
Wrap a wet cloth around the valve body and copper tube
stub to protect it from heat damage.

6.

Braze the line set to the service valve.  Quench the joints
with water or a wet cloth to prevent heat damage to the
valve core and opening port. 

 The tube end must stay

bottomed in the fitting during final assembly to ensure
proper seating, sealing, and rigidity.

7.

Install the fixed orifice ( or thermal expansion valve which
is sold separately and which is approved for use with R-

410A refrigerant) in the liquid line at the indoor coil (see
Refrigerant Metering Device on page 8).

Flushing Existing Line Set and Indoor Coil

This procedure should not be performed on systems
which contain contaminants, such as compressor burn
out.

Required Equipment

The following equipment is needed to flush the existing line
set and indoor coil (see Figure 8):  Two clean R-22 recovery
bottles, an oil-less recovery machine with a “pump down”
feature, and two sets of gauges (one for use with R-22 and
one for use with R-410A).

Figure 8

Flushing Connections

Note:

The inverted R22 cylinder must contain at least the
same amount of refrigerant as was recovered from
the existing system.

When flushing existing line set and/or indoor coil, be sure to
empty all existing traps.  Residual mineral oil can act as an
insulator, preventing proper heat transfer.  It can also clog
the thermal expansion valve, reducing system performance
and capacity.  Failure to properly flush system as explained
in these instructions will void warranty.

   CAUTION

Содержание 4SHP13 series

Страница 1: ...ipment Installation and service performed by unqualified persons can result in property damage personal injury or death WARNING Sharp metal edges can cause injury When installing the unit use care to...

Страница 2: ...t will transmit sound or vibration to the living area or adjacent buildings Install the unit high enough above the ground or roof to allow adequate drainage of defrost water and prevent ice buildup In...

Страница 3: ...ower coil installation instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size 1 Install line voltag...

Страница 4: ...ces for line sets over 50 Thermostat Designations Some connections may not apply Refer to specific thermostat and indoor unit Without Auxiliary Heat With Auxiliary Heat Do not connect C common connect...

Страница 5: ...are some points to consider when placing and installing a high efficiency outdoor unit Placement Be aware that some localities are adopting sound ordinances based on how noisy the unit is at the neigh...

Страница 6: ...e Caulk PVC Pipe Fiberglass Insulation Outside Wall IMPORTANT Refrigerant lines must not contact structure NOTE Similar installation practices should be used if line set is to be installed on exterior...

Страница 7: ...The tube end must stay bottomed in the fitting during final assembly to ensure proper seating sealing and rigidity 7 Install the fixed orifice or thermal expansion valve which is sold separately and...

Страница 8: ...he proper fixed orifice size for each unit In nonstandard applications the fixed orifice provided with the indoor unit may not be Flushing Procedure IMPORTANT The line set and or indoor coil must be f...

Страница 9: ...e of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating Liquid and SuctionLine Service Valves The liquid li...

Страница 10: ...ions and indoor unit must be checked for leaks Using an Electronic Leak Detector 1 Connect the high pressure hose of the manifold gauge set to the suction valve service port Normally the high pressure...

Страница 11: ...the nitrogen cylinder and remove the manifold gauge hose from the cylinder Open the manifold gauge valves to release the nitrogen from the line set and indoor unit 8 Reconnect the manifold gauge to th...

Страница 12: ...If not do not start equipment until the power company has been consulted and the voltage condition corrected 6 Set thermostat for cooling demand turn on power to indoor blower and close the outdoor u...

Страница 13: ...pair any leaks then use the weigh in method to charge the unit 1 Recover the refrigerant from the unit 2 Conduct a leak check then evacuate as previously outlined 3 Weigh in the charge according to th...

Страница 14: ...6 2 7 1 2 6 5 5 7 1 3 6 5 8 7 1 4 6 6 1 8 1 5 6 3 4 8 1 6 6 7 7 8 1 7 6 9 0 9 1 8 6 1 4 9 1 9 6 3 7 9 1 0 7 6 0 0 2 1 7 9 3 0 2 2 7 2 7 0 2 3 7 6 0 1 2 p m e T F e r u s s e r P g i s P 4 7 0 4 1 2 5...

Страница 15: ...ermostats When the room thermostat is placed in the emergency heat position the outdoor unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An ambe...

Страница 16: ...ent accumulated compressor run time period during one thermostat run cycle This time period must occur before a defrost cycle is initiated The defrost interval can be adjusted to 30 T1 60 T2 or 90 T3...

Страница 17: ...from operating at its most efficient level Turn all electric power to unit OFF at disconnect switch es before performing any maintenance operations on system Unit may have multiple power supplies Elec...

Страница 18: ...outdoor coil may require frequent cleaning depending on environmental conditions Clean the outdoor coil with an unpressurized water hose to remove surface contaminants and debris It may be necessary t...

Страница 19: ..._______ Installer _________________________________ City ___________________ State ______________ Unit Model No ______________ Serial No ___________________ Service Technician ________________________...

Страница 20: ...Page 20 of 24 506762 01 Issue 1143...

Страница 21: ...506762 01 Page 21 of 24 Issue 1143 Wiring Diagram for 3 Phase 230 V Models...

Страница 22: ...Page 22 of 24 506762 01 Issue 1143 Wiring Diagram for 3 Phase 460V Models...

Страница 23: ...er is unable to provide warranty service check online at www alliedair com 3 Be prepared to furnish the following information a complete model and serial number b proof of required periodic maintenanc...

Страница 24: ...3 Modification change or alteration of the unit except as expressly directed in writing by Allied Air 4 Improper use accident neglect or unreasonable use or operation of the unit including operation o...

Отзывы: