Allied Air 4SHP13 series Скачать руководство пользователя страница 3

506762-01

Page 3  of  24

Issue 1143

If the 4SHP13 unit is being installed with a new indoor coil
and line set, the refrigerant connections should be made as
outlined in this section.  If an existing line set and/or indoor
coil will be used to complete the system, refer to this section
as well as the section that follows entitled:  

Flushing Existing

Line Set and Indoor Coil

.

If this unit is being matched with an approved line set or indoor
coil which was previously charged with R22 refrigerant, the
line set and coil must be flushed prior to installation.  If the
unit is being used with an existing indoor coil which was
equipped with a liquid line which served as a metering device
(RFCI), the liquid line must be replaced prior to the installation
of the 4SHP13 unit.

• Locate unit away from overhanging roof lines which would

allow water or ice to drop on, or in front of, coil or into
unit.

Slab Mounting

When installing a unit at grade level, install on level slab
high enough above grade so that water from higher ground
will not collect around the u nit (see Figure 2).

Roof  Mounting

Install unit at a minimum of 6” above surface of the roof to
avoid ice buildup around the unit.  Locate the unit above a
loard bearing wall or area of the roof that can adequately
support the unit.  Consult local codes for rooftop applications.

Electrical  Wiring

All field wiring must be done in accordance with the National
Electrical Code (NEC) recommendations, Canadian
Electrical Code (CEC) and CSA Standards, or local codes,
where applicable.

Unit must be grounded in accordance with national and
local codes.  Failure to ground unit properly can result in
personal injury or death.

  WARNING

Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
rating plate for minimum circuit ampacity and maximum
overcurrent protection size.

1. Install line voltage power supply to unit from a properly

sized disconnect switch.  Any excess high voltage field
wiring should be trimmed or secured away from the low
voltage field wiring.

2. Ground unit at unit disconnect switch or to an earth ground.

To facilitate conduit, a hole is in the bottom of the control
box.  Connect conduit to the control box using a proper
conduit fitting.  Units are approved for use only with copper
conductors.  24V Class II circuit connections are made in
the low voltage junction box.  A complete unit wiring
diagram is located inside the unit control box cover (see
wiring diagram in this instruction).

3. Install room thermostat on an inside wall that is not subject

to drafts, direct sunshine, or other heat sources.

4. Install low voltage wiring from outdoor to indoor unit and

from thermostat to indoor unit (see Figure 3 on page 4).

5. Do not bundle any excess 24V control wire inside control

box.  Run control wire through installed wire tie and tighten
wire tie to provide low voltage strain relief and to maintain
separation of filed-installed low and high voltage circuits.

Refrigerant Piping

Figure 2

Slab Mounting

Discharge Air

Mounting Slab

Ground Level

Building

Structure

Refrigerant can be harmful if inhaled. Refrigerant must
always be used and recovered responsibly.  Incorrect or
irresponsible use of refrigerant can result in personal injury
or death.

   WARNING

Line voltage is present at all components when unit is
not in operation on units with single pole contractors.
Disconnect all remote electric power supplies before
opening access panel.  Unit may have multiple power
supplies.  Failure to disconnect all power supplies could
result in personal injury or death.

   WARNING

Содержание 4SHP13 series

Страница 1: ...ipment Installation and service performed by unqualified persons can result in property damage personal injury or death WARNING Sharp metal edges can cause injury When installing the unit use care to...

Страница 2: ...t will transmit sound or vibration to the living area or adjacent buildings Install the unit high enough above the ground or roof to allow adequate drainage of defrost water and prevent ice buildup In...

Страница 3: ...ower coil installation instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size 1 Install line voltag...

Страница 4: ...ces for line sets over 50 Thermostat Designations Some connections may not apply Refer to specific thermostat and indoor unit Without Auxiliary Heat With Auxiliary Heat Do not connect C common connect...

Страница 5: ...are some points to consider when placing and installing a high efficiency outdoor unit Placement Be aware that some localities are adopting sound ordinances based on how noisy the unit is at the neigh...

Страница 6: ...e Caulk PVC Pipe Fiberglass Insulation Outside Wall IMPORTANT Refrigerant lines must not contact structure NOTE Similar installation practices should be used if line set is to be installed on exterior...

Страница 7: ...The tube end must stay bottomed in the fitting during final assembly to ensure proper seating sealing and rigidity 7 Install the fixed orifice or thermal expansion valve which is sold separately and...

Страница 8: ...he proper fixed orifice size for each unit In nonstandard applications the fixed orifice provided with the indoor unit may not be Flushing Procedure IMPORTANT The line set and or indoor coil must be f...

Страница 9: ...e of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating Liquid and SuctionLine Service Valves The liquid li...

Страница 10: ...ions and indoor unit must be checked for leaks Using an Electronic Leak Detector 1 Connect the high pressure hose of the manifold gauge set to the suction valve service port Normally the high pressure...

Страница 11: ...the nitrogen cylinder and remove the manifold gauge hose from the cylinder Open the manifold gauge valves to release the nitrogen from the line set and indoor unit 8 Reconnect the manifold gauge to th...

Страница 12: ...If not do not start equipment until the power company has been consulted and the voltage condition corrected 6 Set thermostat for cooling demand turn on power to indoor blower and close the outdoor u...

Страница 13: ...pair any leaks then use the weigh in method to charge the unit 1 Recover the refrigerant from the unit 2 Conduct a leak check then evacuate as previously outlined 3 Weigh in the charge according to th...

Страница 14: ...6 2 7 1 2 6 5 5 7 1 3 6 5 8 7 1 4 6 6 1 8 1 5 6 3 4 8 1 6 6 7 7 8 1 7 6 9 0 9 1 8 6 1 4 9 1 9 6 3 7 9 1 0 7 6 0 0 2 1 7 9 3 0 2 2 7 2 7 0 2 3 7 6 0 1 2 p m e T F e r u s s e r P g i s P 4 7 0 4 1 2 5...

Страница 15: ...ermostats When the room thermostat is placed in the emergency heat position the outdoor unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An ambe...

Страница 16: ...ent accumulated compressor run time period during one thermostat run cycle This time period must occur before a defrost cycle is initiated The defrost interval can be adjusted to 30 T1 60 T2 or 90 T3...

Страница 17: ...from operating at its most efficient level Turn all electric power to unit OFF at disconnect switch es before performing any maintenance operations on system Unit may have multiple power supplies Elec...

Страница 18: ...outdoor coil may require frequent cleaning depending on environmental conditions Clean the outdoor coil with an unpressurized water hose to remove surface contaminants and debris It may be necessary t...

Страница 19: ..._______ Installer _________________________________ City ___________________ State ______________ Unit Model No ______________ Serial No ___________________ Service Technician ________________________...

Страница 20: ...Page 20 of 24 506762 01 Issue 1143...

Страница 21: ...506762 01 Page 21 of 24 Issue 1143 Wiring Diagram for 3 Phase 230 V Models...

Страница 22: ...Page 22 of 24 506762 01 Issue 1143 Wiring Diagram for 3 Phase 460V Models...

Страница 23: ...er is unable to provide warranty service check online at www alliedair com 3 Be prepared to furnish the following information a complete model and serial number b proof of required periodic maintenanc...

Страница 24: ...3 Modification change or alteration of the unit except as expressly directed in writing by Allied Air 4 Improper use accident neglect or unreasonable use or operation of the unit including operation o...

Отзывы: