Allied Air 4SHP13 series Скачать руководство пользователя страница 13

506762-01

Page 13  of  24

Issue 1143

Low pressure gauge to suction line service valve

High pressure gauge to liquid line service valve

2.

Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of R-410A.

3.

If room temperature is below 70° F, set the room thermostat
to call for heat. This will create the necessary load for
properly charging the system in the cooling cycle.

4.

Use a digital thermometer to record the outdoor ambient
temperature.

5.

When the heating demand has been satisfied, switch
the thermostat to cooling mode with a set point of 68° F.
When pressures have stabilized, use a digital
thermometer to record the liquid and suction line
temperatures.

6.

The outdoor temperature will determine which charging
method to use. Proceed with the appropriate charging
method.

Charge Using Weigh-In Method (Fixed Orifice/TXV
Systems)

If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, first locate and repair any leaks then
use the weigh-in method to charge the unit.

1.

Recover the refrigerant from the unit.

2.

Conduct a leak check, then evacuate as previously
outlined.

3.

Weigh in the charge according to the total amount shown
on the unit nameplate.

If weighing facilities are not available or if unit is being
charged during warm weather, follow one of the other
procedures outlined below.

Charge Using Subcooling Method (Fixed Orifice/TXV
Systems) – Outdoor Temperatures 65° F or Above

If charging a fixed orifice or TXV system when the outdoor
ambient temperature is 65° F or above, the subcooling
method can be used to charge the unit.

1.

With the manifold gauge hose on the liquid service port
and the unit operating stably, use a digital thermometer
to record the liquid line temperature.

2.

At the same time, record the liquid line pressure reading.

3.

Use the temperature/pressure chart (Table 5) to
determine the saturation temperature for the liquid line
pressure reading.

Figure 12

Use gauge ports on suction line valve and liquid line valve for evacuation refrigerant lines and indoor
coil.  Use suction gauge to measure suction pressure during charging.

Cooling Cycle

Содержание 4SHP13 series

Страница 1: ...ipment Installation and service performed by unqualified persons can result in property damage personal injury or death WARNING Sharp metal edges can cause injury When installing the unit use care to...

Страница 2: ...t will transmit sound or vibration to the living area or adjacent buildings Install the unit high enough above the ground or roof to allow adequate drainage of defrost water and prevent ice buildup In...

Страница 3: ...ower coil installation instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size 1 Install line voltag...

Страница 4: ...ces for line sets over 50 Thermostat Designations Some connections may not apply Refer to specific thermostat and indoor unit Without Auxiliary Heat With Auxiliary Heat Do not connect C common connect...

Страница 5: ...are some points to consider when placing and installing a high efficiency outdoor unit Placement Be aware that some localities are adopting sound ordinances based on how noisy the unit is at the neigh...

Страница 6: ...e Caulk PVC Pipe Fiberglass Insulation Outside Wall IMPORTANT Refrigerant lines must not contact structure NOTE Similar installation practices should be used if line set is to be installed on exterior...

Страница 7: ...The tube end must stay bottomed in the fitting during final assembly to ensure proper seating sealing and rigidity 7 Install the fixed orifice or thermal expansion valve which is sold separately and...

Страница 8: ...he proper fixed orifice size for each unit In nonstandard applications the fixed orifice provided with the indoor unit may not be Flushing Procedure IMPORTANT The line set and or indoor coil must be f...

Страница 9: ...e of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating Liquid and SuctionLine Service Valves The liquid li...

Страница 10: ...ions and indoor unit must be checked for leaks Using an Electronic Leak Detector 1 Connect the high pressure hose of the manifold gauge set to the suction valve service port Normally the high pressure...

Страница 11: ...the nitrogen cylinder and remove the manifold gauge hose from the cylinder Open the manifold gauge valves to release the nitrogen from the line set and indoor unit 8 Reconnect the manifold gauge to th...

Страница 12: ...If not do not start equipment until the power company has been consulted and the voltage condition corrected 6 Set thermostat for cooling demand turn on power to indoor blower and close the outdoor u...

Страница 13: ...pair any leaks then use the weigh in method to charge the unit 1 Recover the refrigerant from the unit 2 Conduct a leak check then evacuate as previously outlined 3 Weigh in the charge according to th...

Страница 14: ...6 2 7 1 2 6 5 5 7 1 3 6 5 8 7 1 4 6 6 1 8 1 5 6 3 4 8 1 6 6 7 7 8 1 7 6 9 0 9 1 8 6 1 4 9 1 9 6 3 7 9 1 0 7 6 0 0 2 1 7 9 3 0 2 2 7 2 7 0 2 3 7 6 0 1 2 p m e T F e r u s s e r P g i s P 4 7 0 4 1 2 5...

Страница 15: ...ermostats When the room thermostat is placed in the emergency heat position the outdoor unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An ambe...

Страница 16: ...ent accumulated compressor run time period during one thermostat run cycle This time period must occur before a defrost cycle is initiated The defrost interval can be adjusted to 30 T1 60 T2 or 90 T3...

Страница 17: ...from operating at its most efficient level Turn all electric power to unit OFF at disconnect switch es before performing any maintenance operations on system Unit may have multiple power supplies Elec...

Страница 18: ...outdoor coil may require frequent cleaning depending on environmental conditions Clean the outdoor coil with an unpressurized water hose to remove surface contaminants and debris It may be necessary t...

Страница 19: ..._______ Installer _________________________________ City ___________________ State ______________ Unit Model No ______________ Serial No ___________________ Service Technician ________________________...

Страница 20: ...Page 20 of 24 506762 01 Issue 1143...

Страница 21: ...506762 01 Page 21 of 24 Issue 1143 Wiring Diagram for 3 Phase 230 V Models...

Страница 22: ...Page 22 of 24 506762 01 Issue 1143 Wiring Diagram for 3 Phase 460V Models...

Страница 23: ...er is unable to provide warranty service check online at www alliedair com 3 Be prepared to furnish the following information a complete model and serial number b proof of required periodic maintenanc...

Страница 24: ...3 Modification change or alteration of the unit except as expressly directed in writing by Allied Air 4 Improper use accident neglect or unreasonable use or operation of the unit including operation o...

Отзывы: