background image

Page 2  of  24

506762-01

Issue 1143

INSTALLATION

Check the unit rating plate to confirm specifications are
as ordered.

Location of Unit

Outdoor units operate under a wide range of weather
conditions; therefore, multiple factors must be considered
when positioning the unit.  The unit must be positioned to
give adequate clearances for sufficient airflow and
serviceing.  Refer to Figure 1 for installation clearances.

General
Read this entire instruction manual, as well as the
instructions supplied in separate equipment, before
starting the installation.  Observe and follow all
warnings, cautions, instructional labels, and tags.
Failure to comply with these instructions could result
in an unsafe condition and/or premature component
failure.

These instructions are intended as a general guide only for
use by qualified personnel and do not supersede any national
or local codes in any way.  The installation must comply with
all provincial, state, and local codes as well as the National
Electrical Code (U.S.) or Canadian Electrical Code (Canada).
Compliance should be determined prior to installation.

4SHP13 condensing units use R-410A which is an ozone-
friendly HFC refrigerant.  The unit must be installed with a
matching indoor coil and line set.  A filter drier approved for
use with R-410A is installed in the unit.

When servicing or repairing HVAC components, ensure the
fasteners are appropriately tightened. Table 1 shows torque
values for fasteners.

• Place a sound-absorbing material, such as Isomode,

under the unit if it will be installed in a location or position
that will transmit sound or vibration to the living area or
adjacent buildings.

• Install the unit high enough above the ground or roof to

allow adequate drainage of defrost water and prevent ice
buildup.

• In heavy snow areas, do no locate the unit where drifting

snow will occur.  The unit base should be elevated above
the depth of average snows.

NOTE:  Elevation of the unit may be accomplished by
constructing a frame using suitable materials.  If a
support frame is constructed, it must not block drain
holes in unit base.

• When installed in areas where low ambient temperatures

exist, locate unit so winter prevailing winds do not blow
directly into outdoor coil.

Inspection of Shipment

Upon receipt of equipment, carefully inspect it for possible
shipping damage.  If damage is found, it should be noted on
the carrier’s freight bill.  Take special care to examine the
unit inside the carton if the carton is damaged.  Any
concealed damage discovered should be reported to the
last carrier immediately, preferably in writing, and should
include a request for inspection by the carrier’s agent.

If any damages are discovered and reported to the carrier
DO NOT INSTALL THE UNIT

, as claim may be denied.

Torque Table

Table 1

Compressor Bolts

90 in. lbs.

#10 Machine Screws

28 in. lbs.

#8 Machine Screws

16 in. lbs.

Sheet Metal Screws

16 in. lbs.

Service Port Caps

8 ft. lbs.

Stem Caps

8 ft. lbs.

Fastener

Torque

Figure 1

Installation Clearances

* A service clearance of 30" must be maintained on one of the

sides adjacent to the control box. Clearance to one of the other
three sides must be 36". Clearance to one of the remaining two
sides may be 12" and the final side may be 6".

A clearance of 24" must be maintained between units.

48" clearance required on top of unit. Maximum soffit overhang is
36".

Содержание 4SHP13 series

Страница 1: ...ipment Installation and service performed by unqualified persons can result in property damage personal injury or death WARNING Sharp metal edges can cause injury When installing the unit use care to...

Страница 2: ...t will transmit sound or vibration to the living area or adjacent buildings Install the unit high enough above the ground or roof to allow adequate drainage of defrost water and prevent ice buildup In...

Страница 3: ...ower coil installation instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size 1 Install line voltag...

Страница 4: ...ces for line sets over 50 Thermostat Designations Some connections may not apply Refer to specific thermostat and indoor unit Without Auxiliary Heat With Auxiliary Heat Do not connect C common connect...

Страница 5: ...are some points to consider when placing and installing a high efficiency outdoor unit Placement Be aware that some localities are adopting sound ordinances based on how noisy the unit is at the neigh...

Страница 6: ...e Caulk PVC Pipe Fiberglass Insulation Outside Wall IMPORTANT Refrigerant lines must not contact structure NOTE Similar installation practices should be used if line set is to be installed on exterior...

Страница 7: ...The tube end must stay bottomed in the fitting during final assembly to ensure proper seating sealing and rigidity 7 Install the fixed orifice or thermal expansion valve which is sold separately and...

Страница 8: ...he proper fixed orifice size for each unit In nonstandard applications the fixed orifice provided with the indoor unit may not be Flushing Procedure IMPORTANT The line set and or indoor coil must be f...

Страница 9: ...e of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses must be rated for use at up to 800 psi of pressure with a 4000 psi burst rating Liquid and SuctionLine Service Valves The liquid li...

Страница 10: ...ions and indoor unit must be checked for leaks Using an Electronic Leak Detector 1 Connect the high pressure hose of the manifold gauge set to the suction valve service port Normally the high pressure...

Страница 11: ...the nitrogen cylinder and remove the manifold gauge hose from the cylinder Open the manifold gauge valves to release the nitrogen from the line set and indoor unit 8 Reconnect the manifold gauge to th...

Страница 12: ...If not do not start equipment until the power company has been consulted and the voltage condition corrected 6 Set thermostat for cooling demand turn on power to indoor blower and close the outdoor u...

Страница 13: ...pair any leaks then use the weigh in method to charge the unit 1 Recover the refrigerant from the unit 2 Conduct a leak check then evacuate as previously outlined 3 Weigh in the charge according to th...

Страница 14: ...6 2 7 1 2 6 5 5 7 1 3 6 5 8 7 1 4 6 6 1 8 1 5 6 3 4 8 1 6 6 7 7 8 1 7 6 9 0 9 1 8 6 1 4 9 1 9 6 3 7 9 1 0 7 6 0 0 2 1 7 9 3 0 2 2 7 2 7 0 2 3 7 6 0 1 2 p m e T F e r u s s e r P g i s P 4 7 0 4 1 2 5...

Страница 15: ...ermostats When the room thermostat is placed in the emergency heat position the outdoor unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An ambe...

Страница 16: ...ent accumulated compressor run time period during one thermostat run cycle This time period must occur before a defrost cycle is initiated The defrost interval can be adjusted to 30 T1 60 T2 or 90 T3...

Страница 17: ...from operating at its most efficient level Turn all electric power to unit OFF at disconnect switch es before performing any maintenance operations on system Unit may have multiple power supplies Elec...

Страница 18: ...outdoor coil may require frequent cleaning depending on environmental conditions Clean the outdoor coil with an unpressurized water hose to remove surface contaminants and debris It may be necessary t...

Страница 19: ..._______ Installer _________________________________ City ___________________ State ______________ Unit Model No ______________ Serial No ___________________ Service Technician ________________________...

Страница 20: ...Page 20 of 24 506762 01 Issue 1143...

Страница 21: ...506762 01 Page 21 of 24 Issue 1143 Wiring Diagram for 3 Phase 230 V Models...

Страница 22: ...Page 22 of 24 506762 01 Issue 1143 Wiring Diagram for 3 Phase 460V Models...

Страница 23: ...er is unable to provide warranty service check online at www alliedair com 3 Be prepared to furnish the following information a complete model and serial number b proof of required periodic maintenanc...

Страница 24: ...3 Modification change or alteration of the unit except as expressly directed in writing by Allied Air 4 Improper use accident neglect or unreasonable use or operation of the unit including operation o...

Отзывы: