![ALLIANCE YU120E Скачать руководство пользователя страница 25](http://html.mh-extra.com/html/alliance/yu120e/yu120e_installation-operation-and-maintenance-manual_2901134025.webp)
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Installation
23
70458101 (EN)
Connect inlet hoses to water supply. Flush the lines for
approximately two minutes to remove any foreign
materials that could clog the screens in the water
mixing valve. This is especially important when
installing a tumble dryer in a newly constructed or
renovated building. Then connect the hoses to the
Y-valve; connect the Y-valve to the connections at the
rear of the tumble dryer.
IMPORTANT: Thread hose couplings onto valve
connections finger tight, then turn 1/4 turn with
pliers. Do not cross thread or overtighten
couplings.
IMPORTANT: Hoses and other natural rubber
parts deteriorate after extended use. Hoses may
develop cracks, blisters or material wear from the
temperature and constant high pressure they are
subjected to.
All hoses should be checked on a yearly basis for
any visible signs of deterioration. Any hose showing
the signs of deterioration listed above should be
replaced immediately. All hoses should be replaced
every five years.
NOTE: Longer inlet hoses are available (as
optional equipment at extra cost) if the hoses
supplied with the tumble dryer are not long enough
for installation. Order hoses as follows:
Part No. 20617 Inlet hose 2.44 m (8 feet)
Part No. 20618 Inlet hose 3.05 m (10 feet)
NOTE: Replacement outlet hoses are available (at
extra cost). Order 44073302 Hose, 53 cm (21 in.) for
120 series and 44073303, 79 cm (31 in.) for 170 and
200 series.
Electrical Requirements
No independent external power source or supply
connection is necessary. Power to operate the 24 Volt
fire suppression system is from the rear junction/
contactor box.
Auxiliary Alarm
The fire suppression system provides an auxiliary
output signal when the system is activated. During
tumble dryer installation, you have the option to
connect a separate alarm system to this auxiliary
output. Potential uses of the auxiliary output include,
but are not limited to: (1) sounds an alarm, (2)
activates a building sprinkler system, (3) notifies a fire
department, etc. Use of the auxiliary output is not
required for the fire suppression system to operate, but
may be used for additional protection.
The connection to the auxiliary output is made through
the FS-1 and FS-2 fast-on connections inside the fire
suppression control box. Refer to
Figure 5
. The relay
is rated for 24 VAC, 5.2 Amp, sealed current.
NOTE: The auxiliary output is activated during
fire suppression system maintenance test sequence.
Consider this fact prior to your system test every
three months. (Example: If the external system
uses the auxiliary output to call the fire
department, inform the fire department before and
after the fire suppression system maintenance test.)
Figure 5
Electrical power must be provided to
tumbler at all times. The fire suppression
system will be inoperative if the main
electrical power supply is disconnected.
W690
WARNING
TMB1999N
1
Opening for Auxiliary Alarm Cable
2
Fuse
3
Auxiliary Alarm Fast-On Connection
4
Test Button
5
Light
6
Reset Button
7
Auxiliary Alarm Fast-On Connection
TMB1999N
3
4
5
6
7
1
2