Horizontal Exhaust Installation: Exhaust Air Flow Maximum Length of Duct 30 feet [9.1 m]
D686I_SVG
8
6
5
7
A
B
C
D
E
F
G
H
I
J
K
9
3
2
4
1
1.
Where the exhaust duct pierces a combustible wall or ceiling, the opening must be sized per local codes.
2.
Wall
3.
2 in. [50 mm] Minimum or Clearance per Local Codes
4.
No Screen or Cap
5.
24 in. [610 mm] Minimum Clearance to Roof/Ground
6.
Exhaust Outlet
7.
Air Flow
8.
30 °
9.
Clean Out Cover - Inspect Monthly
Figure 25
Duct Station
Minimum Diameter of
Collector Duct
A
4 inches [102 mm]
B
8 inches [203 mm]
C
9 inches [229 mm]
D
10 inches [254 mm]
E
11 inches [279 mm]
F
12 inches [305 mm]
G
13 inches [326 mm]
H
14 inches [356 mm]
I
15 inches [381 mm]
J
15 inches [381 mm]
K
16 inches [406 mm]
Table 5
Installation
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
29
Part No. 805419R3