Vertical Exhaust Installation
D753I_SVG
7
2
6
5
4
3
1
1.
Roof
2.
24 in. [610 mm] Minimum Clearance to Roof/Ground
3.
No Screen or Cap
4.
Wall
5.
2 in. [50 mm] Minimum
6.
Where the exhaust duct pierces a combustible wall or ceil-
ing, an opening must be sized as shown or per local codes.
7.
Connect to Dryer
Figure 26
WARNING
To reduce the risk of fire and the accumulation of
combustion gases, DO NOT exhaust dryer air into a
window well, gas vent, chimney or enclosed, unven-
tilated area, such as an attic, wall, ceiling, crawl
space under a building or concealed space of a
building.
W045
A Backdraft Damper, Part No. 58786 (obtain locally),should be
installed in a 4 inch [102 mm] diameter VERTICAL duct system.
This will prevent a backdraft when dryer is not in use, and will
keep the exhaust air in balance within the central exhaust system.
Position and Level the Unit
WARNING
Units elevated above floor level must be anchored to
that elevated surface, base or platform. The material
used to elevate the unit should also be anchored to
the floor to ensure that the unit will not walk or that
the unit can not be physically pulled, tipped or slid
from its installed position. Failure to do so may re-
sult in conditions which can produce serious injury,
death and/or property damage.
W307
1. Position unit so it has sufficient clearance for installation and
servicing.
SWD1006N_SVG
C
E
E
A
B
D
NOTE: Shaded areas indicate adjacent structure.
Dryer and Exhaust Duct Clearances
Area
Description
Minimum
Clearance
A
Left Dryer Side
0 in. [0 mm]
B
Right Dryer Side 1 in. [25 mm]
C
Dryer Top
6 in. [152 mm]
D *
Dryer Rear
4 in. [102 mm]
Table continues...
Installation
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
30
Part No. 805419R3