© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
9
506126
Step 3: (Gas Dryer Only) Connect Gas
Supply Pipe
1. Make certain your dryer is equipped for use with
the type of gas in your laundry room. Dryer is
equipped at the factory for
Natural Gas
with a
3/8 inch NPT gas connection.
NOTE: The gas service to a gas dryer must
conform with the local codes and ordinances, or in
the absence of local codes and ordinances, with the
latest edition of the National Fuel Gas Code ANSI
Z223.1/NFPA 54 or the CAN/CSA-B149.1 Natural
Gas and Propane Installation Code.
Natural Gas
, 1000 Btu/ft
3
(37.3 MJ/m
3
) service must
be supplied at minimum 5.0 inch water column
pressure to maximum 10.5 inch water column
pressure.
For proper operation at altitudes above 2500 feet
(760 m) the natural gas valve spud orifice size must be
reduced to ensure complete combustion. Refer to
.
2. Remove the shipping cap from the gas
connection at the rear of the dryer. Make sure you
do not damage the pipe threads when removing
the cap.
3. Connect to gas supply pipe using a new flexible
stainless steel connector.
NOTE: When connecting to a gas line, an
equipment shut-off valve must be installed within
6 feet (1.8 m) of the dryer. An 1/8 in. NPT pipe plug
must be installed as shown for checking inlet
pressure. Refer to
.
.
To reduce the risk of gas leaks, fire or
explosion:
• The dryer must be connected to the type
of gas as shown on nameplate located in
the door recess.
• Use a new flexible stainless steel
connector.
• Use pipe joint compound insoluble in L.P.
(Liquefied Petroleum) Gas, or Teflon tape,
on all pipe threads.
• Purge air and sediment from gas supply
line before connecting it to the dryer.
Before tightening the connection, purge
remaining air from gas line to dryer until
odor of gas is detected. This step is
required to prevent gas valve
contamination.
• Do not use an open flame to check for gas
leaks. Use a non-corrosive leak detection
fluid.
• Any disassembly requiring the use of
tools must be performed by a suitably
qualified service person.
W316
WARNING
Natural Gas Altitude Adjustments
Altitude
Orifice Size
Part No.
feet
m
No.
inches
mm
3000
915
43
0.0890
2.26
503778
6000
1830
44
0.0860
2.18
58719
8000
2440
45
0.0820
2.08
503779
9000
2740
46
0.0810
2.06
503780
10,000
3050
47
0.0785
1.99
503781
Table 2
D233I
1
New stainless steel flexible connector –
(Use design CSA certified connector)
Use only if allowed by local codes
2
1/8 in. NPT Pipe Plug
3
Equipment Shut-Off Valve
4
Black Iron Pipe
Shorter than 20 ft. (6.1 m) –
Use 3/8 in. (9.5 mm) pipe
Longer than 20 ft. (6.1 m) –
Use 1/2 in. (12.7 mm) pipe
5
3/8 in. NPT Gas Connection
Figure 5
D
1
3
2
4
5
Содержание 506126R5