Page 15
3.11 SET UP SYSTEM
Returning to the Program Menu, select F2 to establish the
initial system configurations. Then select F1 later to estab-
lish specific RTD configurations. The ESC key may be se-
lected at any time to back out of the selection.
3.12 SYSTEM TIME
Select F1 to enable the cursor field. Enter military time in
this format: HH:MM:SS then press Enter or PgDn to pro-
ceed. PgUp previous menu.
3.13 SYSTEM DATE
Select F1 to change the date. Enter the date in this format
MM/DD/YY then select Enter or PgDn to proceed. PgUp pre-
vious menu.
3.14 SYSTEM NAME
Enter a name unique for this monitor. When configuration
and history reports are viewed, this monitor name will ap-
pear. Some installations may incorporate several monitors.
Select F1 to edit, and enter or PgDn to save.
3.15 SYSTEM FAULT RELAY
(section 10)
This relay is common to all 4 RTD channels. F1 toggles and
selects the latching and non-latching operation of the system
fault relay. The fault relay output is accessible at TB3 figure
6. This relay is designed for failsafe (normally energized)
and remains in this condition unless power is removed from
the monitor or a fault occurs. Select PgDn to proceed. PgUp
previous menu.
3.16 PRE-ALARM RELAY
This relay is the RTD first temperature trip point relay and is
common to all 4 channels. This relay defaults to non-
latching. Select F1 to change to latching. The pre-alarm re-
lay output, figure 6, is accessible at TB3. Select PgDn to
proceed. PgUp previous menu.
3.17 PRE-ALARM MESSAGE
Enter F1 and type an optional message that references any
four channels to this pre-alarm. The pre-alarm occurs when
an RTD attains it’s first set-point threshold and trips the dedi-
cated pre-alarm relay. Refer to figure 6 for location of relay
contacts.
3.18 SAVING THE DATA for the F2 SET UP SYSTEM
Select PgDn to return to the main menu then select ESC,
then F1.
*
PRE-ALARM RELAY *
NON-LATCHING
F1-CHNG PGU/D-NXT
*
SYSTEM FAULT RELAY *
NON-LATCHING
F1-CHNG PGU/D-NXT
* SYSTEM NAME *
Pump #2
F1-CHNG PGU/D-NXT
* SYSTEM DATE *
MM/DD/YY
F1-CHNG PGU/D-NXT
* PROGRAM MENU *
F1 SET UP RTD
F2 SET UP SYSTEM
F3 CHANGE PASSWORD
* SYSTEM TIME *
HH:MM:SS
F1-CHNG PGU/D-NXT
*
PRE-ALARM MESSAGE *
F1-CHNG PGU/D-NXT