Troubleshooting
7-3
MOD Status Indicator
Status
Cause
Corrective Action
Off
The adapter is not
powered.
•
Securely connect the adapter to the drive
using the ribbon cable.
•
Apply power to the drive.
Flashing
Red
The adapter has failed the
firmware test or the node
address switch setting is
invalid.
•
Verify that node address switch setting is
between 0 and 63.
•
Clear faults in the adapter.
•
Cycle power to the drive.
•
If cycling power does not correct the
problem, the parameter settings may
have been corrupted. Reset defaults and
reconfigure the module.
•
If resetting defaults does not correct the
problem, flash the adapter with the latest
firmware release.
Solid
Red
The adapter has feailed the
hardware test.
•
Cycle power to the drive.
•
Replace the adapter.
Flashing
Green
The adapter is operational,
but is not transferring I/O
data.
•
Place the scanner in RUN mode.
•
Program the controller to recognize and
transmit I/O to the adapter.
•
Configure the adapter for the program in
the controller.
•
Normal behavior if no DPI I/O is enabled.
Solid
Green
The adapter is operational
and transferring I/O data.
•
No Action.