Appendix
D
Logic Command/Status Words
Appendix D provides the definitions of the Logic Command/Logic
Status words that are used for some products that can be connected to the
DeviceNet adapter. If you do not see the Logic Command/Logic Status
for the product that you are using, refer to your product’s documentation.
Logic Command Word
* A 0 = Not Stop condition (logic 0) must first be present before a 1 = Start condition will start the drive.
PowerFlex 70 and PowerFlex 700 Drives
Logic Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Command Description
x Stop
0 = Not Stop
1 = Stop
x
Start*
0 = Not Start
1 = Start
x
Jog
0 = Not Jog
1 = Jog
x
Clear
Faults
0 = Not Clear Faults
1 = Clear Faults
x x
Direction
00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Direction Control
x
Local
Control
0 = No Local Control
1 = Local Control
x
MOP
Increment
0 = Not Increment
1 = Increment
x x
Accel Rate 00 = No Command
01 = Accel Rate 1 Command
10 = Accel Rate 2 Command
11 = Hold Accel Rate
x
x
Decel Rate 00 = No Command
01 = Decel Rate 1 Command
10 = Decel Rate 2 Command
11 = Hold Decel Rate
x
x
x
Reference
Select
000 = No Command
001 = Ref. 1 (Ref A Select)
010 = Ref. 2 (Ref B Select)
011 = Ref. 3 (Preset 3)
100 = Ref. 4 (Preset 4)
101 = Ref. 5 (Preset 5)
110 = Ref. 6 (Preset 6)
111 = Ref. 7 (Preset 7)
x
MOP
Decrement
0 = Not Decrement
1 = Decrement
Содержание PowerFlex 20-COMM-D
Страница 1: ...DeviceNet Adapter 20 COMM D FRN 1 xxx User Manual...
Страница 6: ...iv Table of Contents Notes...
Страница 72: ...6 14 Using Explicit Messaging Notes...
Страница 90: ...B 8 Adapter Parameters Notes...
Страница 122: ...C 32 DeviceNet Objects Notes...
Страница 132: ...E 8 Master Slave I O Configuration Notes...
Страница 148: ......