10
MicroLogix™ Analog Input/Output Module
Publication 1762-IN005A-US-P
Differential Sensor Transmitter Types
NOTE
Grounding the cable shield at the module end only usually
provides sufficient noise immunity. However, for best cable
shield performance, earth ground the shield at both ends, using
a 0.01µF capacitor at one end to block AC power ground
currents, if necessary.
IN 0 (+)
IN 0 (-)
V out 0
V out 1
I out 0
I out 1
COM
IN 1 (-)
IN 1 (+)
COM
Analog Sensor
Analog Load