Rockwell Automation Publication 445L-IN005A-EN-P - May 2018

GuardShield Micro 400 Safety Light Curtains

The Micro 400 IP69K option has the Micro 400 light curtains factory 

sealed in polycarbonate enclosures.
The GuardShield Micro 400 requires a controller to operate with one of 

the following safety controllers 

• MSR41 ON/OFF functionality
• MSR42 multifunction module

Proper Use

The GuardShield Micro 400 safety light curtain must be used only as 

defined in the 

Range of Uses of the Device on page 3

. Only qualified 

personnel can use this light curtain and it can only be used on the 

machine that it has been installed on and initialized by qualified 

personnel.
If the device is used for any other purposes or modified in any way, 

warranty claims against Allen-Bradley/Guardmaster become null and 

void.

General Protective Notes and Protective Measures

The national/international rules and regulations apply to the 

installation, use, and periodic technical inspections of the safety light 

curtain, in particular:

• Machine Directive 2006/42/EC
• Low Voltage Directive 2006/95/EC
• Use of Work Directive (2009/104/EC)
• The work safety regulations/safety rules
• Other relevant health and safety regulations

Manufacturers and users of the machine with which the safety light 

curtain is used are responsible for obtaining and observing all applicable 

safety regulations and rules.
The notices, in particular the test regulations of these installation 

instructions (for example, on use, mounting, installation, or integration 

into the existing machine controller) must be observed.
Specialist personnel or specially qualified and authorized personnel 

must conduct, record, and document the tests to confirm that the tests 

can be reconstructed and retraced at any time.
The installation instructions must be made available to the user of the 

machine where the GuardShield Micro 400 safety light curtain is 

installed. The machine operator is to be instructed in the use of the 

device by specialist personnel and must be instructed to read the 

installation instructions.

Product Description

This section provides information on the special features and properties 

of the safety light curtain. It describes the structure and functions of the 

unit, in particular the different operating modes.
Read this section before you mount, install, and commission the unit.

Special Features

• Slim design 15 x 20 mm (0.59 x 0.79 in.)
• Built in diagnostic LEDs
• HW configurable with MSR41
• HW and SW configurable with MSR42
• M12 connector on 508 mm (20 in.) pigtails
• Low maintenance and cost-effective

Principle of Operation

The GuardShield Micro 400 safety light curtain consists of a non-

matched pair of optic units, for example, transmitter and receiver with 

the same protected height and resolution. The controller functionality 

of the Micro 400 light curtains is through a separate control module. 

• MSR41 ON/OFF functionality
• MSR42 multifunction module

The maximum distance between transmitter and receiver is referred to 

as the protective field width or range. The protective field height is the 

distance between the first and last beam in the device.
The transmitter emits sequential pulses of infrared light, which the 

GuardShield Micro 400 receives and processes by the connected 

controller. The connected MSR controller synchronizes the timing of 

the emission and reception of the infrared light pulses.
The connected controller has safety outputs [Output Signal Switching 

Devices (OSSDs)] and nonsafety auxiliary outputs. When the 

GuardShield Micro 400 transmitter and receiver are properly connected 

and aligned, the OSSDs of the connected controller are current sourcing 

+24V DC. Interruption of the sensing field causes the controller to 

switch the sourced current OFF (0V DC).
When you restore the GuardShield Micro 400 sensing field (in Guard 

only configuration), it causes safety outputs (OSSDs) of the controller 

to switch to the active high state (resume current so24V DC).

The GuardShield Light Curtain

The GuardShield Micro 400 safety light curtain consists of a transmitter 

and a receiver.

Figure 1 - Components of the GuardShield Micro 400

IMPORTANT

Observe the following items to maintain the proper and safe 
use of the GuardShield Micro 400 safety light curtain.

IMPORTANT

Operating mode as manual or automatic restart (reset), EDM 
(external device monitoring), blanked beams, or overriding of 
the GuardShield Micro 400 are controlled from the connected 
safety controller (for example, MSR42). For details, see the user 
manual of the connected safety controller.

Transmitter (white)

Receiver (blue marking)

Содержание GuardShield Micro 400

Страница 1: ...eld Micro 400 is an economical three box transmitter receiver and controller Type 4 safety light curtain offered in a small profile 15 x 20 mm 0 59 x 0 79 in housing The protective heights are offered...

Страница 2: ...r MSR42 and other safety devices in the stop circuit When connecting two cascadable segments together the resultant cable length between segments is 1000 mm 40 in If an additional length between segme...

Страница 3: ...tem is not allowed to start as long as personnel are within the hazardous area See the Examples of Range of Use on page 5 for an illustration of the protective modes Depending on the application mecha...

Страница 4: ...ribes the structure and functions of the unit in particular the different operating modes Read this section before you mount install and commission the unit SpecialFeatures Slim design 15 x 20 mm 0 59...

Страница 5: ...or MSR42 controller The patchcord has an 8 pin M12 on one end and an RJ45 connector on opposite end ExamplesofRangeofUse The GuardShield Micro 400 safety light curtain operates as a proper protective...

Страница 6: ...Resolution mm in Response Time Cascade 1 tN1 1200 14 47 24 0 55 41 9 ms Cascade 2 tN2 300 14 11 8 0 55 18 5 ms Standard tLC 600 14 23 62 0 55 26 3 ms System tLC tC tN 1200 14 300 14 600 14 47 24 0 55...

Страница 7: ...second when the operator begins reaching toward the point of operation hazard from rest Ts Stop time of the machine tool that is measured at the final control element Tcs Response time of the control...

Страница 8: ...nimumDistancefromReflectingSurfaces The infrared light from the transmitter can be reflected off shiny surfaces and received by the system receiver If this condition occurs it can result in an object...

Страница 9: ...ngitudinalaxesofbothareorientedparalleltoeachother Averticalorhorizontalmountinglevelcanhelp to find the correct position Take care that the receiver and transmitter are oriented in the same direction...

Страница 10: ...ir Figure 11 Multiple GuardShield Micro 400 Alignment Options CascadedGuardShieldMicro400 ConfigurationofOperatingModesinCascadingSystems The operating modes of a cascaded GuardShield Micro 400 can be...

Страница 11: ...h for cleaning 4 Clean polycarbonate enclosure as follows Remove dirt on the enclosure using ample quantities of water In that way you avoid scratching the surface Then wipe off with a clean slightly...

Страница 12: ...ry The following color code is defined White Transmitter Tx Blue Receiver Rx Table 4 Connection Cables Table 5 Extension Cables The RJ45 connector M12 8 pin connector male shielded cable connection ca...

Страница 13: ...orrect interface with a safety PLC or safety relays with positive guided relay contacts Figure 16 Wiring Diagram for Connection of MSR42 to Contactors Length 1 or 3 m 3 28 or 9 8 ft tolerance 0 50 mm...

Страница 14: ...undant semiconductor OSSD Output Signal Switching Device safety outputs One or more MSR45E safety relay expansion modules can be connected to the MSR41 or MSR42 controller Each MSR41 or MSR42 safety c...

Страница 15: ...voltage to the MSR41 or MSR42 safety controller 2 Transmitter and or receiver cables not correctly plugged into the MSR41 or MSR42 controller 3 Transmitterandreceiverlightcurtainsareconnectedtotheinco...

Страница 16: ...receiver In the middle between transmitter and receiver 7 No hazardous machine movement while the test rod is anywhere within the protective field 8 If the blanking function is activated check all sec...

Страница 17: ...oduct of Switzerland Operat range 0 to 5m Resolut 14 mm Type 4 Abbreviations Terminology Definition Rx Receiver Tx Transmitter Cat No Catalog number Ser Series number Rev Revision number HW Hardware v...

Страница 18: ...t Synchronization Electrical through MSR41 or MSR42 Wave length 940 nm Time for self check when switching on Usp 5 s Environmental Enclosure type rating Micro 400 is IP54 Micro 400 IP69K is IP65 IP66...

Страница 19: ...in the Rockwell Automation order tool Proposal Works The response time of each pair can be evaluated in the Configuration Tool software or is provided on the product label Sensor Pair Transmitter Rece...

Страница 20: ...5 150 5 91 0 8 kg 28 2 oz 445L C4C0300FP 445L G4C0300FP 445L F4C0300FP 14 0 55 300 11 81 0 9 kg 31 7 oz 445L C4C0450FP 445L G4C0450FP 445L F4C0450FP 14 0 55 450 17 71 0 9 kg 31 7 oz 445L C4C0600FP 445...

Страница 21: ...7 28 4 1 12 34 1 34 468 50 18 42 0 Protective Height A 111 55 4 39 Protective Height A 90 3 54 38 5 1 51 15 0 59 58 2 28 Protective Length B 32 5 1 28 50 55 1 99 System Cat No Mounting Kit Included P...

Страница 22: ...cat no for each ribbon cable connector Table 16 Safety Relay Interface Accessories for MSR41 or MSR42 Controllers Description Mounting Size Catalog Number MSR41 ON OFF 35 mm DIN Rail 22 5 0 89 440R P2...

Страница 23: ...connection of additional devices for example enabling switch emergency stop button Table 17 Optical Interface Table 18 Optional Accessories Description Catalog Number USB optical interface software c...

Страница 24: ...profile is catalog number 450L AM SM Drawings of this mounting kit are provided in publication 450L IN002 Optional mounting kits catalog number 445L AF6140 or 445L AF6141 are also available for detai...

Страница 25: ...re clearly recognized as surfaces with the integrated optical lenses The not monitored areas passive elements are also clearly indicated as black surfaces HowtoCalculatetheSafetyDistanceSforGuardShiel...

Страница 26: ...figurations For those systems longer lead time can be expected The mentioned response times in Table 23 on page 27 are maximum values The times depend on the controller type and the configuration The...

Страница 27: ...45L P4C0950FP 445L T4C0950FP 445L R4 C0950FP 14 0 55 20 x 15 950 37 4 35 4 1 3 kg 45 86 oz 445L P4C1000FP 445L T4C1000FP 445L R4C1000FP 14 0 55 20 x 15 1000 39 37 36 7 1 3 kg 45 86 oz 445L P4C1100FP 4...

Страница 28: ...14 0 55 20x15 700 27 56 28 9 1 kg 35 27 oz 445L C4C0800FP 445L G4C0800FP 445L F4C0800FP 14 0 55 20x15 800 31 5 31 5 1 1 kg 38 8 oz 445L C4C0850FP 445L G4C0850FP 445L F4C0850FP 14 0 55 20x15 850 33 46...

Страница 29: ...8 kg 98 77 oz 445L 110490 0029 445L 112862 445L 112861 14 0 55 40x30 1050 41 34 38 0 2 9 kg 102 29 oz 445L 110490 0025 445L 111394 445L 111395 14 0 55 40x30 1100 43 31 39 3 3 0 kg 105 82 oz 445L 1104...

Страница 30: ...00 47 24 41 9 3 1 kg 109 35 oz 445L 110491 0007 445L 110183 445L 110182 14 0 55 40x30 1350 53 15 45 8 3 4 kg 119 93 oz 445L 110491 0008 445L 110185 445L 110184 14 0 55 40x30 1500 59 06 49 7 3 7 kg 130...

Страница 31: ...kg 38 8 oz 445L 110490 0007 445L 110131 445L 110130 30 1 18 20 x 15 650 25 59 17 6 1 0 kg 35 27 oz 445L 108582 0002 445L 108578 445L 108579 30 1 18 20 x 15 900 35 43 20 2 1 3 kg 45 86 oz 445L 108670 4...

Страница 32: ...with the provisions of the following EC directives including all applicable amendments 2014 30 EU Electromagnetic Compatibility Directive EMC and 2006 42 EC Machinery Directive MD and that the respec...

Отзывы: