Rockwell Automation Publication 445L-IN005A-EN-P - May 2018

15

GuardShield Micro 400 Safety Light Curtains

4. The OSSD outputs are not connected to +24V DC.
5. The connected switching elements (load) are not connected to 

24V DC.

6. If two or more GuardShield Micro 400 light curtains are to be 

used, make sure that each system is properly installed, to avoid 

optical interference.

Switch on the GuardShield Micro 400 and check its function by 

observing the following: 2 seconds after switching on, the system starts 

to work properly if the protection field is free of obstructions

Troubleshooting

With the help of two LEDs, system conditions and faults of the 

GuardShield Micro 400 systems are indicated.
A red and a green LED are integrated in the end-cap connection module 

of each profile (near the cable), which clearly signals the status of the 

protective field. With the help of the LED display, system conditions and 

faults of the GuardShield Micro 400 systems are indicated.

Figure 18 - Indicators

Table 6 - LED Meanings

The conditions signaled by the LEDs can also be obtained from the 

status outputs of the connected MSR41 or MSR42 control module (see 

MSR41 Safety Module User Manual

 and 

MSR42 Control Module User 

Manual

 of the corresponding control unit).

Continuous red LED: Check the alignment if the LED of the 

GuardShield Micro 400 is continuously red. With the help of the 

optical interface (445L-AF6150), it is possible to display individual 

beam status on a laptop using a USB interface.

Red LED blinking (lockout condition): If the red LED of the 

GuardShield Micro 400 is blinking, the following conditions can cause 

the fault:

1. Inadequate supply voltage to the MSR41 or MSR42 safety 

controller.

2. Transmitter and/or receiver cables not correctly plugged into 

the MSR41 or MSR42 controller.

3. Transmitter and receiver light curtains are connected to the incorrect 

locations in the controller (transmitter plugged into receiver 

connection).

4. Incorrect assembly of cascaded systems (transmitter and receiver 

mixed).

5. Cable connector makes poor contact.
6. Error in the EDM feedback channel at the safety control (only if 

EDM).

7. Short circuit at the OSSD outputs.
8. Foreign light source affects the receiving unit.
9. Blanking configured and wrong light curtain length or 

resolution connected (only if blanking).

Corrective Steps 

1. Examine connections, cables, and plugs of transmitter and 

receiver.

2. Turn the supply voltage off and on again.

With the help of the optical interface, it is possible to display the lock 

out information on a laptop using a USB interface.
If the LED of the safety light curtain is still blinking red, contact 

Rockwell Automation technical support.

Safety Instructions—Maintenance

For safety reasons, all inspection results must be recorded. 
Only persons, who clearly understand the functioning of the 

GuardShield Micro 400 and of the machine, can conduct an inspection.
If the installer, planning engineer and operator are different people, 

make sure that they have sufficient information available to conduct the 

inspection. 

LED

Color

Meaning

Green

On

Protective field is free.

Flashing

Intensity is inadequate.

Red

Off

Protective field is free.

On

Protective field is interrupted.

Flashing

Error (lock out condition)

IMPORTANT

In cascaded systems only the LED in the first safety light 
curtain illuminates (closest to the safety controller).

ATTENTION: 

Never operate the GuardShield Micro 400 before 

conducting the following inspection. Improper inspection can lead 
to operator injury.

Содержание GuardShield Micro 400

Страница 1: ...eld Micro 400 is an economical three box transmitter receiver and controller Type 4 safety light curtain offered in a small profile 15 x 20 mm 0 59 x 0 79 in housing The protective heights are offered...

Страница 2: ...r MSR42 and other safety devices in the stop circuit When connecting two cascadable segments together the resultant cable length between segments is 1000 mm 40 in If an additional length between segme...

Страница 3: ...tem is not allowed to start as long as personnel are within the hazardous area See the Examples of Range of Use on page 5 for an illustration of the protective modes Depending on the application mecha...

Страница 4: ...ribes the structure and functions of the unit in particular the different operating modes Read this section before you mount install and commission the unit SpecialFeatures Slim design 15 x 20 mm 0 59...

Страница 5: ...or MSR42 controller The patchcord has an 8 pin M12 on one end and an RJ45 connector on opposite end ExamplesofRangeofUse The GuardShield Micro 400 safety light curtain operates as a proper protective...

Страница 6: ...Resolution mm in Response Time Cascade 1 tN1 1200 14 47 24 0 55 41 9 ms Cascade 2 tN2 300 14 11 8 0 55 18 5 ms Standard tLC 600 14 23 62 0 55 26 3 ms System tLC tC tN 1200 14 300 14 600 14 47 24 0 55...

Страница 7: ...second when the operator begins reaching toward the point of operation hazard from rest Ts Stop time of the machine tool that is measured at the final control element Tcs Response time of the control...

Страница 8: ...nimumDistancefromReflectingSurfaces The infrared light from the transmitter can be reflected off shiny surfaces and received by the system receiver If this condition occurs it can result in an object...

Страница 9: ...ngitudinalaxesofbothareorientedparalleltoeachother Averticalorhorizontalmountinglevelcanhelp to find the correct position Take care that the receiver and transmitter are oriented in the same direction...

Страница 10: ...ir Figure 11 Multiple GuardShield Micro 400 Alignment Options CascadedGuardShieldMicro400 ConfigurationofOperatingModesinCascadingSystems The operating modes of a cascaded GuardShield Micro 400 can be...

Страница 11: ...h for cleaning 4 Clean polycarbonate enclosure as follows Remove dirt on the enclosure using ample quantities of water In that way you avoid scratching the surface Then wipe off with a clean slightly...

Страница 12: ...ry The following color code is defined White Transmitter Tx Blue Receiver Rx Table 4 Connection Cables Table 5 Extension Cables The RJ45 connector M12 8 pin connector male shielded cable connection ca...

Страница 13: ...orrect interface with a safety PLC or safety relays with positive guided relay contacts Figure 16 Wiring Diagram for Connection of MSR42 to Contactors Length 1 or 3 m 3 28 or 9 8 ft tolerance 0 50 mm...

Страница 14: ...undant semiconductor OSSD Output Signal Switching Device safety outputs One or more MSR45E safety relay expansion modules can be connected to the MSR41 or MSR42 controller Each MSR41 or MSR42 safety c...

Страница 15: ...voltage to the MSR41 or MSR42 safety controller 2 Transmitter and or receiver cables not correctly plugged into the MSR41 or MSR42 controller 3 Transmitterandreceiverlightcurtainsareconnectedtotheinco...

Страница 16: ...receiver In the middle between transmitter and receiver 7 No hazardous machine movement while the test rod is anywhere within the protective field 8 If the blanking function is activated check all sec...

Страница 17: ...oduct of Switzerland Operat range 0 to 5m Resolut 14 mm Type 4 Abbreviations Terminology Definition Rx Receiver Tx Transmitter Cat No Catalog number Ser Series number Rev Revision number HW Hardware v...

Страница 18: ...t Synchronization Electrical through MSR41 or MSR42 Wave length 940 nm Time for self check when switching on Usp 5 s Environmental Enclosure type rating Micro 400 is IP54 Micro 400 IP69K is IP65 IP66...

Страница 19: ...in the Rockwell Automation order tool Proposal Works The response time of each pair can be evaluated in the Configuration Tool software or is provided on the product label Sensor Pair Transmitter Rece...

Страница 20: ...5 150 5 91 0 8 kg 28 2 oz 445L C4C0300FP 445L G4C0300FP 445L F4C0300FP 14 0 55 300 11 81 0 9 kg 31 7 oz 445L C4C0450FP 445L G4C0450FP 445L F4C0450FP 14 0 55 450 17 71 0 9 kg 31 7 oz 445L C4C0600FP 445...

Страница 21: ...7 28 4 1 12 34 1 34 468 50 18 42 0 Protective Height A 111 55 4 39 Protective Height A 90 3 54 38 5 1 51 15 0 59 58 2 28 Protective Length B 32 5 1 28 50 55 1 99 System Cat No Mounting Kit Included P...

Страница 22: ...cat no for each ribbon cable connector Table 16 Safety Relay Interface Accessories for MSR41 or MSR42 Controllers Description Mounting Size Catalog Number MSR41 ON OFF 35 mm DIN Rail 22 5 0 89 440R P2...

Страница 23: ...connection of additional devices for example enabling switch emergency stop button Table 17 Optical Interface Table 18 Optional Accessories Description Catalog Number USB optical interface software c...

Страница 24: ...profile is catalog number 450L AM SM Drawings of this mounting kit are provided in publication 450L IN002 Optional mounting kits catalog number 445L AF6140 or 445L AF6141 are also available for detai...

Страница 25: ...re clearly recognized as surfaces with the integrated optical lenses The not monitored areas passive elements are also clearly indicated as black surfaces HowtoCalculatetheSafetyDistanceSforGuardShiel...

Страница 26: ...figurations For those systems longer lead time can be expected The mentioned response times in Table 23 on page 27 are maximum values The times depend on the controller type and the configuration The...

Страница 27: ...45L P4C0950FP 445L T4C0950FP 445L R4 C0950FP 14 0 55 20 x 15 950 37 4 35 4 1 3 kg 45 86 oz 445L P4C1000FP 445L T4C1000FP 445L R4C1000FP 14 0 55 20 x 15 1000 39 37 36 7 1 3 kg 45 86 oz 445L P4C1100FP 4...

Страница 28: ...14 0 55 20x15 700 27 56 28 9 1 kg 35 27 oz 445L C4C0800FP 445L G4C0800FP 445L F4C0800FP 14 0 55 20x15 800 31 5 31 5 1 1 kg 38 8 oz 445L C4C0850FP 445L G4C0850FP 445L F4C0850FP 14 0 55 20x15 850 33 46...

Страница 29: ...8 kg 98 77 oz 445L 110490 0029 445L 112862 445L 112861 14 0 55 40x30 1050 41 34 38 0 2 9 kg 102 29 oz 445L 110490 0025 445L 111394 445L 111395 14 0 55 40x30 1100 43 31 39 3 3 0 kg 105 82 oz 445L 1104...

Страница 30: ...00 47 24 41 9 3 1 kg 109 35 oz 445L 110491 0007 445L 110183 445L 110182 14 0 55 40x30 1350 53 15 45 8 3 4 kg 119 93 oz 445L 110491 0008 445L 110185 445L 110184 14 0 55 40x30 1500 59 06 49 7 3 7 kg 130...

Страница 31: ...kg 38 8 oz 445L 110490 0007 445L 110131 445L 110130 30 1 18 20 x 15 650 25 59 17 6 1 0 kg 35 27 oz 445L 108582 0002 445L 108578 445L 108579 30 1 18 20 x 15 900 35 43 20 2 1 3 kg 45 86 oz 445L 108670 4...