Publication 1753-RM002C-EN-P - September 2008
91
Technical Safety for the Application Program
Chapter
8
Procedure for Locking the PES
(1)
Locking the PES means locking functions and access from the user
during operation to prevent manipulation of the application program.
The extent of disabling actions depends on the safety requirements for
the particular application of the PES. Consult the approving board in
charge of site acceptance for help in determining the safety
requirements.
Follow these procedure to lock the PES.
1.
The following attribute values must be set in the controller
before compilation:
2.
After loading and starting, you can modify the following
switches in the controller in the following sequence.
a. Start / Restart allowed to FALSE, and
Loading allowed to FALSE.
b. Main Enable to FALSE
.
The only distributed I/O module that can be locked is the 1753-IB20XOB8.
Functions to Lock
Attribute
Value
Main Enable
True
Autostart
True/False
Start/Restart allowed
True
Forcing allowed
False (application-dependent)
Loading allowed
True
Test Mode allowed
False
Stop on Force Timeout
True (application-dependent)
ATTENTION
to
The following switches can be set at other values only
upon consultation with the approving board:
Force Enable
to
TRUE
Stop on Force Timeout
to
TRUE/FALSE
Start / Restart allowed
to
TRUE
Autostart
to
TRUE
ATTENTION
The Test Mode switch must never be set to TRUE for
safety operation.
Содержание GuardPLC 1753
Страница 4: ...4 Publication 1753 RM002C EN P September 2008 Summary of Changes...
Страница 8: ...8 Publication 1753 RM002C EN P September 2008 Table of Contents...
Страница 12: ...12 Publication 1753 RM002C EN P September 2008 Preface...
Страница 84: ...84 Publication 1753 RM002C EN P September 2008 Chapter 7 GuardPLC Controller Operating System...
Страница 96: ...96 Publication 1753 RM002C EN P September 2008 Chapter 8 Technical Safety for the Application Program...
Страница 106: ...106 Publication 1753 RM002C EN P September 2008 Chapter 9 Configuring Communication...
Страница 114: ...114 Publication 1753 RM002C EN P September 2008 Appendix B Use in Central Fire Alarm Systems...
Страница 118: ...118 Publication 1753 RM002C EN P September 2008 Index...
Страница 119: ...Allen Bradley Parts...