![Allen-Bradley GuardPLC 1753 Скачать руководство пользователя страница 65](http://html1.mh-extra.com/html/allen-bradley/guardplc-1753/guardplc-1753_safety-reference-manual_2900190065.webp)
Publication 1753-RM002C-EN-P - September 2008
65
GuardPLC DeviceNet Safety Scanner
Chapter
5
After compiling and downloading the configuration into the GuardPLC and scanner
11
Have all of the application-to-device signal
mappings been verified functionally?
12
Did the RSLogix Guard PLUS! software
compilation process’ calculation of the HSP
signature match the value provided by
RSNetWorx for DeviceNet software in the .ssf
file?
13
Has the system been run long enough under
typical use for the statistics reported in
RSLogix Guard PLUS! and RSNetWorx for
DeviceNet software to be meaningful?
14
Is the Max Scanner Response Time setting on
the GuardPLC controller tab in RSNetWorx for
DeviceNet software greater than the
maximum value reported by the statistics
feature?
15
Have you set the Controller Receive Timeout
as indicated in either 15a or 15b?
15a
For environments with electrical noise
characteristics that do not require HSP retires,
for example, default Controller Resend
Timeout of 0 is acceptable.
Is the Controller Receive Timeout setting
on the HSP Properties dialog in RSLogix
Guard PLUS! software greater than or
equal to the maximum response time
reported on the HSP Protocol tab of the
control panel?
15b
Controller Resend Timeout must be set
greater than zero (HSP retries are necessary
due to an electrically noisy environment):
Is the Controller Resend Timeout setting
on the HSP Properties dialog in RSLogix
Guard PLUS! software greater than or
equal to the maximum response time
reported on the HSP Protocol tab of the
control panel?
Is the Controller Receive Timeout setting
on the HSP Properties dialog in RSLogix
Guard PLUS! software greater than or
equal to N +1 times the Controller Resend
Timeout, where N retries are desired?
16
Is the number of communication time slices
reported on the Statistics tab of the RSLogix
Guard PLUS! software Control Panel equal to
1?
Checklist for Configuration, Programming, and Start-up of
DeviceNet Safety Scanner
Содержание GuardPLC 1753
Страница 4: ...4 Publication 1753 RM002C EN P September 2008 Summary of Changes...
Страница 8: ...8 Publication 1753 RM002C EN P September 2008 Table of Contents...
Страница 12: ...12 Publication 1753 RM002C EN P September 2008 Preface...
Страница 84: ...84 Publication 1753 RM002C EN P September 2008 Chapter 7 GuardPLC Controller Operating System...
Страница 96: ...96 Publication 1753 RM002C EN P September 2008 Chapter 8 Technical Safety for the Application Program...
Страница 106: ...106 Publication 1753 RM002C EN P September 2008 Chapter 9 Configuring Communication...
Страница 114: ...114 Publication 1753 RM002C EN P September 2008 Appendix B Use in Central Fire Alarm Systems...
Страница 118: ...118 Publication 1753 RM002C EN P September 2008 Index...
Страница 119: ...Allen Bradley Parts...