Rockwell Automation Publication 440R-UM013E-EN-P - March 2017
85
Troubleshooting
Chapter 11
Figure 84 - Measure Y32 Voltage
Check the X32 Output
When OUT status indicator is OFF, terminal X32 does not turn ON.
Correct the fault and cycle power. The relay may need to be reconfigured to
correct the fault.
If the PWR/Fault status indicator is green, then measure the voltage at
terminal X32 with a digital multimeter.
(point 1) as the source for the monitoring circuit. The voltage must be around
23V DC. If it is 23V, then follow the circuit and check the voltage at each of
the remaining points (2…6). If X32 measures 0V, then the relay must be
replaced.
Figure 85 - Measure X32 Voltage
TIP
This is proper operation for the EM and EMD relays if they are in a non-
recoverable faulted state. If so, then the PWR/Fault status indicator is solid
red or flashing red.
A2
Y32
A1
23
PLC
Input
Volts
DMM
0V
1
2
3
4
5
Com
OUT
+24V DC
PWR/Fault
CI, DI, DIS or SI
X32
A2
A2
A1
A1
23
S34
Volts
DMM
+24V DC
0V
1
2
3
4
5
PWR/Fault
EM or EMD
CI, DI, DIS or SI
OUT
PWR/Fault
OUT
6
Содержание Guardmaster
Страница 12: ...12 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 1 Overview Notes...
Страница 16: ...16 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 2 Installation Notes...
Страница 34: ...34 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 3 Power Ground and Wire Notes...
Страница 40: ...40 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 4 Configuration Notes...
Страница 50: ...50 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 7 EMD Safety Relay Timing Functions Notes...
Страница 99: ......