Power, Ground, and Wire
Connect a Power Supply
An external 24V DC power supply source must provide power for safety relays.
To comply with the CE (European) Low Voltage Directive (LVD), a DC
source compliant with safety extra low voltage (SELV) or protected extra low
voltage (PELV) must power the safety relays. Bulletin 1606 power supplies are
SELV- and PELV-compliant.
shows the power supply connections. The DI, DIS, EM, EMD, and SI
safety relays have the power supply connections at the top. The CI safety relay,
which is backward compatible with the MSR127 monitoring safety relay, has
A1 at the top and A2 at the bottom.
Figure 7 - Power Supply Connections
Safety Inputs
GSR relays can be connected to the following devices:
• Devices with mechanical contacts
• Devices with OSSD output
• Safety mats
• Safedge™ safety edges
Devices with Mechanical Contacts
The GSR family of safety relays can be connected to safety devices that have
mechanical contacts. The relays can accommodate either 1 N.C. or 2 N.C.
circuits.
shows some of the devices that can be connected to
safety relays.
C24V DC
to Terminal A1
Connect 24V
Common to
Terminal A2
C24V DC
to Terminal A1
Connect 24V
Common to
Terminal A2
DI, DIS, EM,
EMD, and SI
CI
Содержание Guardmaster
Страница 12: ...12 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 1 Overview Notes...
Страница 16: ...16 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 2 Installation Notes...
Страница 34: ...34 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 3 Power Ground and Wire Notes...
Страница 40: ...40 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 4 Configuration Notes...
Страница 50: ...50 Rockwell Automation Publication440R UM013E EN P March 2017 Chapter 7 EMD Safety Relay Timing Functions Notes...
Страница 99: ......