Rockwell Automation Publication 440R-UM013E-EN-P - March 2017
39
Configuration
Chapter 4
Figure 27 - EMD Expansion Relay Status Indicators Flashing in Configuration Mode
5. Cycle the power to store the settings.
After power-up, the current switch settings are compared to the values in
the EEPROM (makes sure that the switches were not changed while
power was off ), and the input and output circuits are checked. Upon
successful completion of the internal checks, the relays are ready for
operation.
IMPORTANT
To keep your GSR relay from permanently faulting, complete the
configuration process by cycling the relay power within 5 minutes of rotary
switch configuration.
0.5s
Flash
2s
Pause
B1 - Indicates that the RANGE Switch is set to 3.
Logic IN - Indicates that the TIME Switch is set to 4